16
z
Wiring diagram for external load controller by voltage/current signal on X62 terminals
X62.5 = functional earth for shield connection
X62.1 = power supply for setpoint changeover
X62.2 = Voltage input DC 0..10V (iput 3)
X62.3 = Current input 4..20mA (iput 3)
X62.4 = Reference ground
z
Wiring diagram for external load controller by voltage/current signal on burner terminal block
If the set-point is to be changed extrernally or load is to be controlled externally by means fo a signal on terminals X62, choose the
signal as follows:
1st level
2nd level
3rd level
4th level
5th level
6th level
Password
Description
Params &
Display
Menu level for
making the parame-
ter settings
LoadControl-
ler
Settings for the inter-
nal load controller
Configuration
General configura-
tion of the load con-
troller
Ext Inp X62 U/I
Service
Configuration of
external input X62:
input signal on X62
can change setpoint
or control the load
4...20 mA
2...10 V
0…10 V
0…20 mA
TEMP./PRES. INPUT
X62.5
Functional earth for
shield connection
X62.3
X62.4
Current input
4...20 mA (input 3)
Reference ground
X62.1
X62.2
Power supply for
setpoint changeover
Voltage input
DC 0...10 V (input 3)
SET POINT INPUT
4...20mA
0...10 V
U
I
+
+
functional earth for shield
connection
power supply for setpoint
changeover
Voltage input DC 0..10V
(iput 3)
Current input 4..20mA (iput
3)
Reference ground
Summary of Contents for P60 VS
Page 45: ...Service manual Siemens LMV 5x M12920CB Rev 1 08 2009...
Page 46: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 97: ...User manual Siemens LMV 5x M12914CA Rev 0 03 2008...
Page 98: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 114: ...Annex1 Example for motor cable...
Page 115: ......
Page 116: ...Annex 2 Example for sensor cable...
Page 117: ......
Page 118: ......
Page 122: ......