C.I.B. UNIGAS - M03957CI
31
11 The burner is factory-set with the head in its MAX position (maximum output). To let the burner operate at a lower output, turn
clockwise the
VRT
screw and move progressively the combustion head back towards the MIN position.
Attention!
if it is necessary to change the head position, repeat the air and gas adjustments described above.
12 the air and gas rate are now adjusted at the maximum output, go on with the point to point adjustment on the
SV1
adjusting cam
as to reach the minimum output point: gradually move the adjusting cam in order to adjust each of the
V1
screws as to set the cam
foil shape as described on the next steps;
13 to change the
SV1
position set the actuator on the manual mode (MAN), turn the adjusting cam
SV1
and set again the actuator to
the AUTO mode to lock the adjusting cam;
14 act on the
V1
screw that mathces the bearings referring to the adjusting cam position;
15 to adjust the next screw, set again the actuator mode to MAN, turn the adjusting cam and set the actuator to AUTO mode to lock
the adjusting cam on the next screw; adjust it and go on this way to adjust all the screws in order to set the cam foil shape, accor-
ding to the combustion values read.
16 Once the cam foil shape is defined, reconnect the
TAB
thermostat reconnecting the wire to the terminal no.6 or setting the RWF40
burner modulator to AUTO or the CMF switch to 3 (only for fully-modulating burner).
17 Turn the burner off, then start it up again.
18 Once the pre-purge time comes to end, drive the burner to the high flame stage by the
TAB
thermostat and check the combustion
values;
19 drive the burner to low flame, if necessary adjust the low flame size (ouput) by inserting a screwdriver on the slot
F
to move the
BF1
cam.
20 The low flame position must never match the ignition position that is why cam
BF1
must be set 20°- 30° more than the ignition posi-
tion (see
ID1
index on previous pictures).
Now adjust the pressure switches (see next paragraph).
VRA
RA
TR
“MAX” head position
“MIN” head position
VRT
SC
SV1
V1
ID1
V1
SV1
Gas throttle valve open
Gas throttle valve closed
BF
F
Summary of Contents for HP60
Page 9: ...C I B UNIGAS M03957CI 9 Overall dimensions mm Boiler recommended drilling template ...
Page 49: ...C I B UNIGAS M03957CI 49 ...
Page 51: ...C I B UNIGAS M03957CI 51 WIRING DIAGRAM Cod 05 680 Progressive burners ...
Page 52: ...C I B UNIGAS M03957CI 52 WIRING DIAGRAM Cod 05 681 Fully modulating burners ...
Page 54: ......
Page 55: ......
Page 56: ......