C.I.B. UNIGAS - M03957CI
14
Gas train connections
The next diagrams show the components of the gas train included in the delivery and which must be fitted by the installer.The diagrams
are in compliance with the current laws.
Key
*Note: the high gas pressure switch can be mounted either upstream the gas valve or downstream the gas valves but upstream the but-
terfly gas valve.
ATTENTION:
BEFORE EXECUTING THE CONNECTIONS TO THE GAS PIPE NETWORK, BE SURE THAT THE
MANUAL CUTOFF VALVES ARE CLOSED. READ CAREFULLY THE “WARNINGS” CHAPTER AT THE BEGINNING
OF THIS MANUAL.
Gas train - 1
Gas train with valves group MB-DLE with built-in gas pressure go VPS504 gas proving system
Gas train - 2
Gas train with valves group VGD 20/40.. with built-in gas pressure go VPS504 gas proving system
Gas train - 3
Gas train with valves group MBC 1200SE (2 gas pressure governor) + VPS504 gas proving system
Gas train - 4
Gas train with valves group MBC 1900/3100/5000SE (2 gas pressure governor) + VPS504 gas proving
system
1
Burner
2
Butterfly valve
3
Gas proving system (option)
4
Maximum gas pressure switch (option*)
5
Minimum gas pressure switch
6
Gas filter
7
Bellow joint
8
Manual cutoff valve
9
MB-DLE Valves group
10
VGD Valves group
18
MBC Valves group (2” with filter provided)
19
MBC Valves group (DN65/80/100)
1
2
3
4
5
7
8
9
4
MANUFACTURER
INSTALLER
3
1
2
5
4
6
7
8
10
4
MANUFACTURER
INSTALLER
1
2
3
4
5
7
8
18
4
MANUFACTURER
INSTALLER
1
2
3
4
7
8
5
6
19
4
MANUFACTURER
INSTALLER
Summary of Contents for HP60
Page 9: ...C I B UNIGAS M03957CI 9 Overall dimensions mm Boiler recommended drilling template ...
Page 49: ...C I B UNIGAS M03957CI 49 ...
Page 51: ...C I B UNIGAS M03957CI 51 WIRING DIAGRAM Cod 05 680 Progressive burners ...
Page 52: ...C I B UNIGAS M03957CI 52 WIRING DIAGRAM Cod 05 681 Fully modulating burners ...
Page 54: ......
Page 55: ......
Page 56: ......