PART III: OPERATION
35
Settable temperature units: °C or °F
Settable pressure units: bar or psi.
choose the desired unit and cofirm by pressing ENTER; press ESC to exit.
choose the temperature and pressure unit and cofirm by pressing ENTER; press ESC to exit.
System lockout
If the system locks out, the following message will appear:
call the Technical Service and tell the message data.
Cold start thermal shock (CSTP)
If the generator cannot suffer thermal shocks, the CSTP (Cold Start Thermal Schock) function can be enabled. This function is already
set by the Technical service (access by reserved password).
if this function is enabled, when the burner starts upthe “Thermal shock protection activated” message will be showed.
If this function is not enabled, after startup, the burner will rapidly increase the load according to the requested value and, if necessary,
to the maximum output.
Manual mode
To by-pass the thermal protection or not to let the buner operate in high flame stage (maximum output) after ignition, the manual mode
is provided.
To choose the manual mode (Manual Operation), use the SELECT arrow keys
Items to be set are the following:
SetLoad
: to set the required load percentage
set the required percentage and confirm by pressing ENTER; press ESC to exit.
choose “Autom/Manual/Off
UnitTemperature
UnitPressure
1
10.08.07
13.47
C:71
D:00
F:
12
Start No.
88
Load
0.0
Gas
OperationalStat
Operation
ManualOperation
Params & Display
SetLoad
Autom/Manual/Off
SetLoad
Curr::
0.0%
New:
20.0%
Summary of Contents for H365X
Page 46: ......
Page 47: ......
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......