PART I: SPECIFICATIONS
14
POWER REDUCTION WITH REFERENCE TO THE BURNER OPERATING CURVE
Since depowering the burner operating range is equivalent to increasing the burner power by the same percentage, the quickest proce-
dure is described point by point below:
Choosing the burner without taking flue gas recirculation into account
estimate the amount of recirculation (see figure below) required to ensure a certain NOx value as a function of the heat load of the
boiler, for that burner
multiply the required burned power by the depowering factor expressed as follows
multiply the back pressure in the combustion chamber by the depressurisation factor squared (pressure losses vary with the
square of the change in flow rate)
choose the burner considering the new power and back pressure value
if the burner size is insufficient, a larger machine must be selected, the depowering factor must be re-checked and the above pro-
cedure repeated.
Gas pressure
in
combustion
h
ead
H365X L-
Stm
3
/h
Ga
s pre
ssu
re
in
combu
stio
n hea
d
H440X L-
Stm
3
/h
H500X L-
Stm
3
/h
Burner pow
er
re
duction %
H365X
Thermic Load (MW/m
3
)
Summary of Contents for H365X
Page 46: ......
Page 47: ......
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......