To determine the performance of a Unicla UWX compressor in a specific application, the following 
Compressor Operation Analysis Report will assist in the collection of the necessary data.

Causes of excessive superheat (discharge)

It is important to note that superheat levels increase as a normal condition

 

• at higher compressor speeds

 

• at higher ambient temperature

Abnormal superheat generation may be caused by one or more of the conditions described below 
and exaggerated under high heat loads.

Low charge rates

There are two reasons for insufficient flow of refrigerant to the compressor to provide adequate 
cooling:

 

• the flow (volume) is reduced giving less cooling medium

 

• excessive low side superheating means the suction vapours are no longer cold

The result is not only a low quantity of cooling vapours, but they are no longer cold.

10.

Normal Superheat/Discharge Line Temperature Chart

330, 440 and 550 series compressors

1800

73

15.5

58

1.86

8.9

15

2200

81

15.5

58

1.86

8.9

23

3500

98

15.5

58

1.86

8.9

40

200 series compressors

1800

77

15.5

58

1.86

8.9

19

2000

78

15.5

58

1.86

8.9

20

3500

93

15.5

58

1.86

8.9

35

170 series compressors

1800

75

15.5

58

1.86

8.9

17

2200

78

15.5

58

1.86

8.9

20

3500

83

15.5

58

1.86

8.9

25

150 series compressors

1800

77

15.5

58

1.86

8.9

19

2200

81

15.5

58

1.86

8.9

23

3600

88

15.5

58

1.86

8.9

30

RPM

Discharge

Temp ˚C

Condensing

Pressure Kgf/cm

2

Condensing

Temp ˚C

Evaporator

Pressure Kgf/cm

2

Compressor 

Inlet Temp ˚C

Superheat

(discharge line)

Summary of Contents for 90 Series

Page 1: ...Compressor Fitting Guidelines for New Applications...

Page 2: ...ining professional information using representative graphs charts and tables Manufacturers specifications must be consulted for specific guidelines and performance data Unicla published data specific...

Page 3: ...selection 6 9 Recommended suction line pipe size 7 8 10 System validation 9 10 11 Other features performance information 11 Note This booklet is designed to assist the installing technician to ensure...

Page 4: ...for 4 5 revolutions to ensure proper lubrication to the working assembly components This will avoid damage during initial start up c Service manual If any disassembly of compressor components is requ...

Page 5: ...drive pulley on the engine and any auxiliary idler or adjusting system Unacceptable alignment is shown in the following diagram b Tension Belt tension adjustment should be made so the belt is taut but...

Page 6: ...e clutch design varies depending on direction of rotation Later generation rubber clutches are designed to operate in both directions making the compressor and clutch assembly multi directional Failur...

Page 7: ...be identical to the native oil already installed to the specific Unicla compressor as identified on the compressor label d Oil separators Oil separators are strongly recommended in multiple evaporato...

Page 8: ...e you have selected the Refrigerating Capacity Graph A complete range of graphs for each model is available from Unicla upon request For single evaporator applications the compressor must cater for th...

Page 9: ...6 16 5 8 0 98 10 16 5 8 0 43 4 5 19 3 4 0 65 6 7 19 3 4 1500 3 6 0 59 6 16 5 8 0 43 4 5 19 3 4 0 72 7 4 19 3 4 0 87 8 9 19 3 4 0 61 6 2 22 7 8 2000 4 9 0 95 9 7 16 5 8 0 70 7 2 19 3 4 0 54 5 6 22 7 8...

Page 10: ...3 8 0 99 10 1 35 1 3 8 2500 26 7 0 64 6 5 28 1 1 8 0 44 4 5 35 1 3 8 0 74 7 6 35 1 3 8 0 89 9 1 35 1 3 8 0 56 5 7 41 1 5 8 3 m Pipe Length 6 m Pipe Length 10 m Pipe Length 12 m Pipe Length 18 m Pipe L...

Page 11: ...rated due to inadequate cooling vapour return to the compressor or excessive external thermal loads on the suction line and or the compressor It is important that all Unicla compressors are operated w...

Page 12: ...educed giving less cooling medium excessive low side superheating means the suction vapours are no longer cold The result is not only a low quantity of cooling vapours but they are no longer cold 10 N...

Page 13: ...quate flow of refrigerant back to the compressor and valuable cooling is not given to the compressor under high heat load conditions This can be diagnosed by determining if a pressure drop is evident...

Page 14: ...la International Limited Unit 1209 1210 12F Manhattan Centre 8 Kwai Cheong Rd Kwai Chung N T Hong Kong Phone 852 2422 0180 Fax 852 2422 0680 Email sales unicla hk Website www unicla hk Unicla Cat No B...

Reviews: