26
Standard
System values
N°
Adjustment range
*
To adjust the pump of the solar energy panels: Set the parameter 29 at the switching off temperature (e.g. 90°C). The hysteresis (parameter 30) can be set, in this
case, between 7 and 25 °C; the standard value is 7 °C.
21
22
23
24
25
26
27
28
29
30
31
32
33
34
20
Introduction of the numeric code
Numeric code
Bus code for heating circuit 1 (HK1)
Bus code for heating circuit 1 (HK2)
Anti frost temperature
Max. flow temperature for flow heating circuit 1
Max. flow temperature for flow heating circuit 2
Heating curves distance
Time relay function
Relay activation temperature (see 28)
Hysteresis for supplementary relay (see 28)
Loading pump stop
Pumps in parallel operation
Anti legionella program
Zone outer compensators communication address
(if in the 0, 1 or 3 setting position no sensor is
connected, the relay is activated with the temporised
program for the circulating pump)
0000-9999
0000-9999
0-15
0-15
(-5)°C - (+5)°C
50°C - 110°C
50°C - 110°C
5 - 50°C
0-3
0: Increase of the return
water temperature
1: Solid fuel fired boiler
2: Manifold pump
3: Solar panel
10°C - 90°C
2 °C - 20°C*
0/1 (Off/On)
0/1 (Off/On)
0/1 (Off/On)
0/1 (Off/On)
Parameter
-----
-----
1
-3
80
45
5
0
5
1
0
1
1
-----
10
FACTORY SET PARAMETERS
(protected by a secret code)
51
Boiler maximum temperature
50°C - 110°C
52
Boiler minimum temperature
10°C - 60°C
53
Temperature increase for D.H.W.
0°C - 50°C
54
Simplified start
10°C - 50°C
55
Activation of minimum temperature limit
0/1 (Off/On)
56
Boiler temperature hysteresis (dynamic)
5 - 20°C
57
Boiler time hysteresis (dynamic)
1 - 30 min
58
Stop time for 2
nd
burner
0 - 30 min
59
Fixed hysteresis for 2
nd
boiler
2 - 20°C
60
Hours to the next boiler sequence change
0 - 250 hours
80
35
20
30
0
5
10
10
2
0
61
Number of starts burner 1
62
Operation time burner 1
63
Number of starts burner 2
64
Operation time burner 2
Mixing valve parameters
71
Operation time of mixing valve 1 (see motor data plate 1)
72
Operation time of mixing valve 2 (see motor data plate 2)
Service
81
Burner relay control
82
Outer sensor control
85
Software version E6
Boiler parameters
30 - 240 s
30 - 240 s
According to configuration
According to configuration
120
120
visualization only
visualization only
visualization only
visualization only
Start with burner relay
Start with outer temperature sensor
visualization only
**
** For TS/3P-DUO the pre-adjusted value is 250.