24
Instruction for the installer
3.12 - ADJUSTMENT OF M 3000 IN SIMPLE
INSTALLATIONS
(M 3000 + Boilers with data communication
capacity)
The connection of just one M 3000 S to a boiler (
with
data
communication capacity) does not require any setting or pro-
gramming intervention: the system is already factory set with
the parameters suitable to the most of low temerature installa-
tions.
If the REGOLAFACILE is NOT installed, the
adjustment of the low temperature circuit will
be done through the manual control PCB,
code 00630130.
A = Potmeter for the adjustment
of the compensation curve.
B = Potmeter for the adjustment
of NON heating outer tempe
rature SOMMER/WINTER)
C = Potmeter for the adjustment
of maximum mixed flow tem
perature.
ATTENTION!
The REGOLAFACILE excludes the adjust-
ments ferom the manual control PCB.
Parameters adjusted on the control
PCB through the switches 1-2-3-4
Switch Position
Description
1
ON
Heating function do not modify)
2
ON
Master Module ON - Slave Module OFF
3
ON
Boiler with data communication capacity
4
OFF
OFF: Module connected directly to the boiler
ON : Module connected (hydraul.) to a water
accumulator tank acqua (see page 29)
A
B
C
ON
OFF
1 2 3 4
ON
(M 3000 + Boiler without data communication
possibility)
The connection of just one M 3000 S to a boiler (
without
data
communication capacity) requires the adjustment of the
switches
1, 2, 3, 4 as shown below: the system is already
factory set with the parameters suitable to the most of low
temerature installations.
If the REGOLAFACILE is NOT installed, the
adjustment of the low temperature circuit will
be done through the manual control PCB,
code 00630130.
A = Potmeter for the adjustment
of the compensation curve.
B = Potmeter for the adjustment
of NON heating outer tempe
rature SOMMER/WINTER)
C = Potmeter for the adjustment
of maximum mixed flow tem
perature.
ATTENTION!
The REGOLAFACILE excludes the adjust-
ments ferom the manual control PCB.
Parameters adjusted on the control
PCB through the switches 1-2-3-4
Switch Position
Description
1
ON
Heating function do not modify)
2
ON
Master Module ON - Slave Module OFF
3
ON
Boiler without data communication capacity
4
OFF
OFF: The boiler controls itself its own temperature
ON : The Module controls the boiler temperature
A
B
C
ON
OFF
1
ON
2 3 4
1 2 3 4
ON
OFF
CONFIGURATION
FOR SOLARE
INTEGRATION**
**
ON
OFF
1 2 3 4
ON