29
Instructions for the installer
3.19 - PROGRAMMING TEMPERATURE WITH
BOILERS CASCADE
Regarding the adjustment or programming of the temperature
controllers, see the booklet enclosed with the individual
Temperature Controller
Following the parameters set in the factory and therefore “can
not be changed.”
Regarding the user-programmable, according to the needs ,
see the instruction manual for Responsible of the installation
.
Default
Personal values
Value range
Designation
INSTALLAZIONE
0000 - 9999
CODE NUMBER
Entry-
0000 - 9999
CODE NUMBER (variation)
0000
(00), 01 - 015
ADDRESS BUS 1
01
(00), 01 - 016
ADDRESS BUS 2
02
00,01 (disins/ins)
VOLTAGE AF
01 (ON)
PROGRAMMABLE PARAMETERS FOR TECHNICIANS, PROTECTED BY CODE NUMBER FOR THERMOREGULATOR
type E8.5064
00, 01 (OFF / ON)
MASTER TEMPERATURE
30 °C - 110 °C
MAX T-MAX CR1 COLLECTOR
10 °C - 80 °C
MIN MIN-T CR1 COLLECTOR
01 (ON)
85 °C
10 °C
0,01
BUS CONNECTION
01
00,01 (disins/ins)
POWER BUS
01 (ON)
2K - 20K
HYSTERESIS
00 - 30 min
TIME HYSTERESIS
00, 01, 02
MINIMUM
5
00 min
00
30 °C - 110 °C
MAX-T CR2
85 °C
......, 01 - 08
ADDRESS BUS BOILER
----
10 °C - 80 °C
MIN-T CR2
10 °C
0 - 11
VOLTAGE CURVE
11
0,00-10,00V
CURVE 11-U2
0V
0,00-10,00V
CURVE 11-U2
10V
00 - 120 °C
CURVE 11-T1
0 °C
00 - 120 °C
CURVE 11-T2
100 °C
0,00-10,00V
CURVE 11-UA
0V
10 °C - 85 °C
WASTE START
10
Only display
BOILER FOUND
00 - 1000kW
POWER LEVEL
* see notes
00,01 (disins/ins)
NEW CONFIGURATION
00 - 100
MINIMUM MODULATION
00
00 - 08
ACS LEVELS
00
(K)
DIFFERENCE REGULATOR
Display
0 - 100%
INDEX POWER RATED
Display
(-99) - 0 - (99)
SWITCHING VALUE
Display
RESTO (min)
TIME BLOCK
Display
50 - 110
°C
MAXIMUM TEMPERATURE BOILERS
85
20 - 500K
DYNAMIC BOILER RISING
30K