30
Start the feed pump by
MAN
activation from the panel, in order to force filling
(the warning light
P1 (2) MODE RUN
lights-up).
Once the MAX level is reached, check the intervention of the HwL high level
safety probe by the switching on of the alarm warning light
HWL SAFE -
PUSH to RESET
on the panel.
Stop the pump
P1 (2)
by turning the
MODE - MAN 0 AUT
selector in
position
0.
Check that the level indication
HWL
corresponds to that indicated on the
adhesive plate
(HIGH)
applied on the side of the level indicator (if the label
is not present, apply it).
Position again the switch
P1 (2) MODE - MAN 0 AUT
in position
AUT
the
pump stops (the warning light
P1 (2) MODE RUN
is off )
Open the discharge line of the generator water
- version with manual discharge: act on the lever valve and hand wheel
- version with automatic discharge: via
MAN
activation frm the panel on
switch
BLD MODE - MAN 0 AUT
During the emptying phase, check switching-off on the panel of the red LED
on the level regulator
HWL SAFE
and the switching-on of the green LED.
Continue emptying the generator beow the SET level to verify that the filler
valve intervenes (the warning light
P(2) MODE RUN
lights-up).
BLD MODE
MAN 0 AUT
MANUAL
AUTOMATIC
P1 MODE
RUN
P2 MODE
RUN
P1 MODE
MAN 0 AUT
P2 MODE
MAN 0 AUT
SET
HIGH
LOW
HWL SAFE
PUSH to RE-
SET
P1 MODE
MAN 0 AUT
P2 MODE
MAN 0 AUT
P1 MODE
MAN 0 AUT
P2 MODE
MAN 0 AUT
ALARM
OK