![Unical BAHR 12 Instructions On Installation, Use And Maintenance Download Page 29](http://html1.mh-extra.com/html/unical/bahr-12/bahr-12_instructions-on-installation-use-and-maintenance_3783645029.webp)
Installation instructions
29
Start-up
Verify that the selector switch ENABLE BURNER OPERATION
BMODE ON
/ OFF
is in position "OFF" (BASIC panel) or "0" (BMI / IML panel), so that the
burner does not start when the panel is powered.
Power the control panel by acting on the main switch.
When the panel is switched on, the level sensors, the luminous alarm but-
tons:
- LWL SAFE 1,
- LWL SAFE 2,
- HWL SAFE (if present),
- TDS SAFE (if present),
light-up and must be reset by pressing the buttons.
Check the panel voltage presence
CP MODE - POWER ON
and burner
power
BMODE POWER ON
warning lights are on.
Start the feed pump by placing the selector switch
P1 (2) MODE - MAN 0
AUT
by
MAN
activation from the panel to check the correct shaft rotation; oth-
erwise, reverse the phases on the CO5 removable power supply connector
of the control panel.
Make sure water reaches the pump, bleed the air from the intake located on
the upper part of the pump body.
Start the feed pump(s) by means
AUT
activation from the panel and fill the
generator (during the filling phase, the warning light
P1 (2) MODE RUN
on
the panel lights-up).
This operation verifies the correct functioning:
- SET probe intervention (IML panel)
- pump OFF probe intervention (BASIC / BMI panel)
When you reach the correct level, the pumps stop automatically (the warning
light
P1 (2) MODE RUN
is off).
Check that the level corresponds to the one indicated on the adhesive plate
applied on the side of the level indicator (if the label is not present, apply it).
Check that there is no leakage through flanged and threaded joints
P1 MODE
MAN 0 AUT
P2 MODE
MAN 0 AUT
P1 MODE
MAN 0 AUT
P2 MODE
MAN 0 AUT
SET
HIGH
LOW
B MODE
OFF ON
B MODE
MAN-0-AUTO
BASIC
IMC/IML
LWL SAFE1
Push to Reset
LWL SAFE2
Push to Reset
HWL SAFE
Push to Reset
TDS SAFE
Push to Reset
CP MODE
POWER ON
B MODE
POWER ON