9.3.1.3 Polarization Index Measurement

Polarization Index (PI) refers to the value of measured resistance in 10 minutes to 

that in 1 minute. It takes 10 minutes to perform polarization index testing. If the time 

of insulation testing is 10 minutes or more, polarization index testing is completed 

and saved.

PI=  

R

10min

R

1min

>4

4~2

2~1

<1.0

Polarization Index (PI)

Insulation condition

Very good

Good

Poor

Dangerous

Press “TIME” button under insulation resistance testing condition without high voltage 

output. When the LCD shows PI, it indicates the tester enters polarization index 

measurement mode.

Then, the LCD shows PI, Time1, Time2, timer symbol, etc. In initial interface, the 

default time of Times is 1 minute, that is 01:00 (the mantissa flashes to indicate 

user can set the parameter). The default time of Time2 is 10 minutes, that is 10:00. 

After completing setting Time1, the tester by default switches to setting state of 

Time2. Press “ENTER” to confirm and save the change, or press “ESC” to cancel 

the change.

Press “TEST” to perform test, the LCD shows basic elements including battery power, 

high-voltage warning symbol, leakage current, real-time output voltage, measured 

insulation resistance (Time1 or Time2), testing value of analog bar graph, Time1 or 

Time2, set countdown time, PI, storage capacity, etc.

When the set time is up, the test ends automatically, the testing indicator light turns 

off, the tester discharges fast, and the LCD shows the testing value. Press       and   

      to cyclically display PI, insulation resistance in Time2, and insulation resistance 

in Time1.

9.3.1.4 Dielectric Absorption Ratio Measurement

Dielectric Absorption Ratio (DAR) refers to the value of insulation resistance in 

1 minute to that in 15 seconds. It takes 1 minute to perform absorption ratio testing. 

The measurement data of all insulation testing in less than 1 minute are deemed 

invalid. If the time of insulation testing is 1 minute or more, the absorption ratio 

testing is included in the result.

DAR=  

R

1min

R

15s

>1.4

1.25~1.0

<1.0

Dielectric Absorption Ratio (DAR)

Insulation condition

Very good

Good

Dangerous

Press “TIME” button under insulation resistance testing condition without high 

voltage output. When the LCD shows DAR, it indicates the tester absorption ratio 

measurement mode.

Then, the LCD shows DAR, Time1, Time2, timer symbol, etc. In initial interface, 

the default time of Time1 is 15 seconds that is 00:15 (the mantissa flashes to 

indicate user can set the parameter). The default time of Time2 is 1 minute that 

is 01:00. After completing setting Time1, the tester by default switches to the 

setting state of Time2. Press “ENTER” to confirm and save the change, or press 

“ESC” to cancel the change.

Press “TEST” to perform test, the LCD shows basic elements including battery 

power, high-voltage warning symbol, leakage current, real-time output voltage, 

measured insulation resistance (Time1 or Time2), testing value of analog bar 

graph, Time1 or Time2, set countdown time, DAR, storage capacity, etc.

When the set time is up, the test ends automatically, the testing indicator light 

turns off, the tester discharges fast, and the LCD shows the testing value. 

Press      and      to cyclically display DAR, insulation resistance in Time2, and 

insulation resistance in Time1.

UT512D/E User Manual

UT512D/E User Manual

Summary of Contents for UT512D

Page 1: ...UT512D UT512E 2 5kV Insulation Resistance Tester User Manual P N 110401111817X...

Page 2: ...Trend guarantees that the product is free from any defect in material and workmanship within one year from the purchase date This warranty does not apply to damages caused by accident negligence misu...

Page 3: ...ainly used to measure insulation resistance of cable motor power generator transformer mutual inductor high voltage switch lightning arrester and more it is an ideal measurement meter for electric pow...

Page 4: ...T512E 8 PCS LR14 alkaline batteries UT512D Error limit a of reading b digits one year warranty Environment temperature 23 5 Environment humidity 45 75 RH In the table below The humidity must be less t...

Page 5: ...ications UT512E Function Measurement range Accuracy Remark Low resistance measurement Open circuit voltage 5V Note If the measured resistance is 20 the buzzer alarms if 660 660 is displayed The short...

Page 6: ...bidden to use the tester without battery cover set in place otherwise it may pose a risk of electric shock Keep fingers behind the finger guard when perform measurement do not touch exposed wire conne...

Page 7: ...plug red lead GUARD Grounding protection outlet single plug green lead EARTH High resistance measurement outlet single plug black lead LCD segmented display screen Functional buttons USB port Carryin...

Page 8: ...testing Bluetooth Insulation resistance measurement mode AC DC voltage measurement mode Power on off Increase select high range or previous group of data Decrease adjust time and resistance cyclically...

Page 9: ...ress this button to switch to insulation resistance testing function V UT512E AC DC voltage testing button Without high voltage output short press V button to switch to AC DC voltage testing mode The...

Page 10: ...measurement Data deletion button In READ state short press CLR and then press ENTER to delete current data press ESC to exit data deletion function In READ state the symbol CLR and the storage capaci...

Page 11: ...rged if low battery occurs please replace with battery in same type 9 2 Battery Charging UT512E When charging with battery charger in power on state the battery power indicator and the charging symbol...

Page 12: ...hange Press TEST to perform test the LCD shows basic elements including battery power high voltage warning symbol leakage current real time output voltage measured insulation resistance testing value...

Page 13: ...tion resistance in Time1 9 3 1 4 Dielectric Absorption Ratio Measurement Dielectric Absorption Ratio DAR refers to the value of insulation resistance in 1 minute to that in 15 seconds It takes 1 minut...

Page 14: ...s if insulation resistance is less than comparison resistance the symbol FAIL will appear on the LCD otherwise PASS appears To return to the continuous measurement interface please press COMP in COMP...

Page 15: ...ltage input the danger symbol flashes in such case do not press the test button to measure resistance as shown in figure 9 3 4 2 Under resistance measurement function connect the black grounding lead...

Page 16: ...rminal with the exterior conductor of inner insulation layer and the unused cable Surface leakage current is conducted to the safety terminal so as to eliminate the surface leakage current at the meas...

Page 17: ...Red XI Maintenance Clean the casing 1 Wipe the surface using soft cloth or sponge dipped with water 2 Do not immerse the tester in water to avoid tester damage 3 Do not store the tester if it is wet 4...

Reviews: