II. Accessories

III.  Safety Information

Thank you for purchasing the High-Voltage Insulation Resistance Tester. The 
product is designed, manufactured and tested in accordance with IEC61010 
Safety Standard (safety requirements of electric measurement products), 
Double Insulation, and Overvoltage CAT IV 600V Standard. Before first use, 
please read and follow the safety information and the precautions in the user 
manual, so as to avoid electric shock or personal injury.

Warning

   

Please read the user manual thoroughly and follow the “Safety Information” strictly. 

   

Keep the user manual with you for use at any time.

   

Use the tester according to the operating instructions.

   

Follow the operating instructions strictly, failure to follow can cause personal injury and product 

    damage.

   

Please wear insulation gloves before use.

   

Do not measure circuit with voltage over 750VAC or 1000VDC.

   

It is forbidden to test near inflammable environment, spark cause explosion.

   

Do not perform operation with tester surface or user’s hands wet. 

   

Please avoid short circuit occurs between metal part and test lead when measuring voltage, 

    otherwise it may cause personal injury.

   

Do not exceed the upper range when performing measurement.

   

Do not start testing when the test leads are not connected properly.

   

Do not open the battery cover during measurement.

   

Do not touch the measured circuit during or right after insulation resistance measurement, 

    otherwise it may cause electric shock.

   

Please stop testing if dirt or carbide susceptible to damaging insulation characteristic is found 

    with test lead or port.

   

Please do not short-circuit or connect test lead when measuring insulation resistance, misoperation 

    may accidentally cause test to be stopped or LED to be lit off. Top end of test lead will discharge 
    when test lead is short-circuited or connected, please note that certain discharge can deteriorate 
    the product performance.

   

Please check the tester and the test lead before use for any damage or defect. Please stop 

    using the tester if test lead or casing insulation is damaged, LCD shows nothing, or the tester 
    cannot work normally.

   

It is forbidden to use the tester without battery cover set in place, otherwise it may pose a risk 

    of electric shock.

   

Keep fingers behind the finger guard when perform measurement, do not touch exposed wire, 

     connector, alligator clip, etc. to avoid electric shock.

   

The output voltage at right position before measurement, it is forbidden to switch over the output 

     voltage during measurement to avoid product damage.

   

If the battery power indicator shows less than one “segment” of power left, please charge or 

    replace the battery immediately to ensure measurement accuracy. Remove the battery if the 
    product is not used for a long time. Power off the tester before opening the battery cover.

   

Do not alter the internal wiring without authorization to avoid product damage and safety hazard.

   

Do not store or use the tester in flammable and explosive environments, or environments with 

    high temperature, high humidity, and strong electromagnetic field.

   

Please clean the casing using soft cloth and mild detergent, do not use abrasive or solvent to 

     avoid casing corrosion and product damage.

   

If insulation on probe is damaged, replace a new one which should meet EN 61010-031 standard, 

    rated follow parameters of the product or better.

   

Before each use verify tester operation by measuring a known voltage.

   

Indoor use only

Red high-voltage test lead: 1 pc   
Green test lead: 1 pc    Black test lead: 1 pc

0℃~35℃; <75%rh

-20℃~60℃; <80%rh

<2000m

2

CAT Ⅳ 600V

IEC61010-1; EN IEC 61010-2-034; 
BS EN 61010-1; BS EN IEC 61010-2-034

230mm(L)x161mm(W)x90mm(D)

About 1800g (including battery)

Dimensions

Weight

Test leads

Operating environment

Storage environment

Altitude

Pollution degree

CAT rating

Safety standards

Please check if any accessory in the package is missing or damaged:
1. User manual: 1 pc
2 Test lead (red, black, green: 1 for each): 3 pcs

3 USB cable: 1 pc

4 Lithium battery charger (model: CS36M168200M1; specification: 
    Input:100-240Vac (Fluct10%), 50/60Hz, 0.8A,Output: 16.8Vdc, 2A: 

    1 pc (UT512E)
5 Lithium battery pack (installed inside the tester, model: UT-M18, 

    specification: 14.8V, 5200mAh): 1 pc (UT512E)
6 Adapting charging stand (optional accessory, model: UT-W12, for UT512E only)

7 8 PCS LR14 alkaline batteries (UT512D)

8 Carrying strap:1pc

    If any missing or damaged accessory occurs, please contact with the supplier 
    immediately.

UT512D/E User Manual

UT512D/E User Manual

Summary of Contents for UT512D

Page 1: ...UT512D UT512E 2 5kV Insulation Resistance Tester User Manual P N 110401111817X...

Page 2: ...Trend guarantees that the product is free from any defect in material and workmanship within one year from the purchase date This warranty does not apply to damages caused by accident negligence misu...

Page 3: ...ainly used to measure insulation resistance of cable motor power generator transformer mutual inductor high voltage switch lightning arrester and more it is an ideal measurement meter for electric pow...

Page 4: ...T512E 8 PCS LR14 alkaline batteries UT512D Error limit a of reading b digits one year warranty Environment temperature 23 5 Environment humidity 45 75 RH In the table below The humidity must be less t...

Page 5: ...ications UT512E Function Measurement range Accuracy Remark Low resistance measurement Open circuit voltage 5V Note If the measured resistance is 20 the buzzer alarms if 660 660 is displayed The short...

Page 6: ...bidden to use the tester without battery cover set in place otherwise it may pose a risk of electric shock Keep fingers behind the finger guard when perform measurement do not touch exposed wire conne...

Page 7: ...plug red lead GUARD Grounding protection outlet single plug green lead EARTH High resistance measurement outlet single plug black lead LCD segmented display screen Functional buttons USB port Carryin...

Page 8: ...testing Bluetooth Insulation resistance measurement mode AC DC voltage measurement mode Power on off Increase select high range or previous group of data Decrease adjust time and resistance cyclically...

Page 9: ...ress this button to switch to insulation resistance testing function V UT512E AC DC voltage testing button Without high voltage output short press V button to switch to AC DC voltage testing mode The...

Page 10: ...measurement Data deletion button In READ state short press CLR and then press ENTER to delete current data press ESC to exit data deletion function In READ state the symbol CLR and the storage capaci...

Page 11: ...rged if low battery occurs please replace with battery in same type 9 2 Battery Charging UT512E When charging with battery charger in power on state the battery power indicator and the charging symbol...

Page 12: ...hange Press TEST to perform test the LCD shows basic elements including battery power high voltage warning symbol leakage current real time output voltage measured insulation resistance testing value...

Page 13: ...tion resistance in Time1 9 3 1 4 Dielectric Absorption Ratio Measurement Dielectric Absorption Ratio DAR refers to the value of insulation resistance in 1 minute to that in 15 seconds It takes 1 minut...

Page 14: ...s if insulation resistance is less than comparison resistance the symbol FAIL will appear on the LCD otherwise PASS appears To return to the continuous measurement interface please press COMP in COMP...

Page 15: ...ltage input the danger symbol flashes in such case do not press the test button to measure resistance as shown in figure 9 3 4 2 Under resistance measurement function connect the black grounding lead...

Page 16: ...rminal with the exterior conductor of inner insulation layer and the unused cable Surface leakage current is conducted to the safety terminal so as to eliminate the surface leakage current at the meas...

Page 17: ...Red XI Maintenance Clean the casing 1 Wipe the surface using soft cloth or sponge dipped with water 2 Do not immerse the tester in water to avoid tester damage 3 Do not store the tester if it is wet 4...