5
109838-01 - 5/20
X-PV
Installation, Operating & Service Manual
Figure 2.1: General Configuration
2
Specifications
(1)
Input ratings can be used for elevations up to 2000 ft above sea level. Refer to Appendix B for elevations 2000 ft or higher.
(2)
Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15. Consult manufacturer before selecting boiler for
installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
X-PV Space Heating Ratings
# of Sections
‘A’
Width
Connection
Size
Water
Content
Approx.
Shipping
Weight
Optional
Direct Vent
Conversion
Kit
Basic
Boiler
Model
Fuel
Input
(1)
Heating
Capacity
Net AHRI
Rating,
Water
(2)
AFUE
Gas
Vent
MBH
MBH
MBH
%
(inch)
(NPT)
(inch)
(gal)
(lbs)
(PN)
X-PV3N
NAT. GAS
70
60
52
85.0
3
12-3/4
1/2
3
2
260
110019-03
X-PV4N
NAT. GAS
105
90
78
85.0
4
15-1/2
1/2
3
3
310
110019-04
X-PV5N
NAT. GAS
140
120
104
85.0
5
18-1/2
1/2
3
4
360
110019-05
X-PV6N
NAT. GAS
175
150
130
85.0
6
21-1/2
1/2
3
5
415
110019-06
X-PV7N
NAT. GAS
210
179
156
85.0
7
24-3/4
3/4
3
6
470
110019-07
X-PV8N
NAT. GAS
245
208
181
84.0
8
27-3/4
3/4
4
7
525
110019-08
X-PV3P
PROPANE
63
54
47
85.0
3
12-3/4
1/2
3
2
260
110019-03
X-PV4P
PROPANE
94.5
81
70
85.0
4
15-1/2
1/2
3
3
310
110019-04
X-PV5P
PROPANE
126
108
94
85.0
5
18-1/2
1/2
3
4
360
110019-05
X-PV6P
PROPANE
157.5
135
117
85.0
6
21-1/2
1/2
3
5
415
110019-06
X-PV7P
PROPANE
189
161
140
85.0
7
24-3/4
3/4
3
6
470
110019-07
X-PV8P
PROPANE
220.5
187
163
84.0
8
27-3/4
3/4
4
7
525
110019-08
Table 2.2: Specifications
Electrical Requirements: 120VAC, 60 Hz, less than 12A
Maximum Allowable Working Pressure - 50 psi. Boiler shipped from factory with a 30 psi safety relief valve.