background image

TFP480

Page 10 of 12

Installation 

The RAPID RESPONSE Model RCP-

1 Residential Control Panel described 

herein must be installed and maintained 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Associa-

tion, in addition to the requirements of 

any other authorities having jurisdiction. 

Failure to do so may impair the perfor-

mance of this device. 
The Model RCP-1 Residential Control 

Panel may be surface-mounted or re-

cessed-mounted with a separately or-

dered bezel. In either case the Model 

RCP-1 Panel must be located in an area 

not subject to freezing. 
Field connections are as follows: 

• 

Water Supply Line 

• 

System Riser Line 

• 

Drain Line 

• 

Electrical 

NOTICE

Do not attempt to reprogram the Model 

RCP-1 Panel. If assistance is required, 

contact Technical Services at Tyco Fire 

Suppression & Building Products. 

Electrical Field Wiring 

The Electronic Control has been 

shipped with resistors located across 

all required contact points. 

NOTICE

Remove resistors only when instruct-

ed to do so. Failure to do so may lead 

to improper conditions or failure of 

the Model RCP-1 Panel to function 

properly. 
The cover is electrically bonded to the 

enclosure ground terminal by means of 

an 18 AWG conductor. Do not remove 

the electrical bond. 
Do not place any wiring in contact with 

CPVC pipe and fittings. Plasticizers, 

such as those found in flexible wire in-

sulation, can damage the pipe and fit-

tings through contact resulting in dam-

age/failure to the system. 

Wiring Notification Appliances 

(Optional) 

Notification appliances (horns) are op-

tional for waterflow alarms (that is, re-

lease of water into the system). 
Adhere to the following guidelines when 

wiring NAC1: 

• 

Remove the 10K, 1/2 W resistor from 

the NAC1 terminals. 

• 

All wiring must be from 12 AWG 

(maximum) to 18 AWG (minimum). 

• 

Conductors must test free of all 

grounds. 

• 

Terminal designations “+” or “-” are 

for alarm state. 

• 

Maximum alarm current is 1A, and 

the maximum distance from the 

Model RCP-1 Panel to the last de-

vice is as follows: 

 

- 210 feet for 18 AWG wiring

 

- 334 feet for 16 AWG wiring

 

- 532 feet for 14 AWG wiring

 

- 845 feet for 12 AWG wiring. 

• 

Terminate circuit with a 10K, 1/2 W 

end-of-line resistor (Figure 4). 

Wiring Relay Connections (Op-

tional)

These connections provide optional 

monitoring by a central control station 

or for a remote signal on premise. Ad-

here to the following guidelines when 

wiring relay modules: 

• 

All wiring must be from 12 AWG 

(maximum) to 18 AWG (minimum). 

• 

Conductors must test free of all 

grounds. 

• 

Relay circuits are rated for 2 A at 30 

VDC, pilot duty (0.35 power factor). 

• 

Circuit is not supervised. 

• 

All relays are single pole, double 

throw. Refer to Figure 5 to set select-

able jumpers for normally open or 

normally closed jumpers. 

• 

Refer to Figure 6 for recommenda-

tion on wiring a remote signal on 

premise. As shown, an alarm, super-

visory, or trouble signal will result in 

activation of the remote signal. 

Wiring AC Power and Batteries

Step 1. 

Close the Main Control Valve 

and open the Main Drain Valve. 

Step 2. 

Place the Air Compressor Dis-

connect switch in the OFF position. 

Step 3. 

Connect the batteries using the 

provided harness per Figure 7. Leave 

one of the connections unconnected as 

shown until directed otherwise. 

Step 4. 

At the power supply junction 

box, connect the Model RCP-1 Panel 

to a dedicated branch circuit per all lo-

cal codes. 
IDC1 will go into alarm. Silence the 

alarm by pressing the SIGNAL SI-

LENCE KEY Accept the alarm condi-

tion by momentarily pressing the AC-

CEPT SIGNAL KEY. 
System Trouble will be indicated for 

lack of the battery connection. Accept 

the trouble condition by momentarily 

pressing the ACCEPT SIGNAL KEY. 
A Supervisory Condition will be indicat-

ed due to the Main Control Valve being 

closed. Acknowledge the supervisory 

condition by momentarily pressing the 

ACCEPT SIGNAL KEY. 

Step 5. 

Connect the remaining battery 

connection. 
The system may now be set for service.

TO

ELECTRONIC

CONTROL

BLACK

LEAD

WHITE

LEAD

(SERIES

JUMPER)

RED LEAD

BATTERIES

FIGURE 7 

BATTERY HARNESS

Summary of Contents for RAPID RESPONSE RCP-1

Page 1: ...des the following features Pre wired assembly containing pre programmed control panel system performance gauges and an en closed compressor Pre engineered riser design Supervised system valve system P...

Page 2: ...is document The Model 4004R Household Fire Warning Unit Subassembly Electronic Control installed within the Model RCP 1 cabinet is UL and C UL Listed Maximum Water Pressure 175 psi 12 1 bar Friction L...

Page 3: ...tically maintained at a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Com pressor Switch Air Compressor Fig ure 2 In the standby condition water is prevented from entering the...

Page 4: ...BLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm...

Page 5: ...NORMALLY CLOSED PRESSURE SWITCH POTTER ELECTRIC PS10 2 INCREASE 16 1 PSI DECREASE 8 1 PSI TUBING TO SYSTEM WATER SUPPLY PRESSURE GAUGE FLOW TUBING TO SYSTEM AIR SUPPLY PRESSURE GAUGE SPRING LOADED CHE...

Page 6: ...ill functioning the Electronic Con trol is using battery power to oper ate The cause for loss of AC Power should be determined and correct ed The system is in a normal stand by condition when only the...

Page 7: ...re System or main control valve closure Step 5 Reset the system as soon as possible In Case of Alarm Condition Step 1 Verify that a fire condition ex ists and take appropriate action that is evacuate...

Page 8: ...10k 1 2 W 3 3k 1 2 W 3 3k 3 3k RAC 1 RAC 2 NAC 1 NAC 2 12 18 AWG 1A MAX NOTIFICATION CIRCUIT IDC 2 IDC 1 IDC 4 IDC 3 1 2 W 3 3k SPM 2 SPM 1 R SOLENOID PRE CONNECTED YEL RED TYPICAL 430687 TWIST ON WIR...

Page 9: ...TS LOWER RIGHT HAND CORNER OF ELECTRONIC CONTROL JUMPER SELECTION OPTIONS RELAY CONTACTS SET ALL RELAY JUMPERS TO NORMALLY OPEN JUMPER RIGHT AUXILIARY POWER TERMINALS UPPER RIGHT HAND CORNER OF ELECTR...

Page 10: ...Maximum alarm current is 1A and the maximum distance from the Model RCP 1 Panel to the last de vice is as follows 210 feet for 18 AWG wiring 334 feet for 16 AWG wiring 532 feet for 14 AWG wiring 845...

Page 11: ...se the Flow Test Valve The Water Supply Gauge should drop to a previously noted re sidual pressure and then return to the normal static pressure Step 4 Perform a lamp test by press ing and holding the...

Page 12: ...mber Step 5 Upon completing the program ming check place the PROGRAM SWITCH in the OFF position and then return the Operator Interface card to its normal position NOTICE Exercise care to ensure that a...

Reviews: