TFP480

Page 5 of 12

AIR

COMPRESSOR

1/20 HP, 115 VAC

PRESET

10 PSI MIN.

14 PSI MAX.

MAIN

CONTROL VALVE

(NORMALLY

OPEN)

SOLENOID

VALVE

(NORMALLY

CLOSED UNTIL

ENERGIZED)

WATER SUPPLY

SYSTEM INLET

CONNECTION

(1 or 1-1/2 INCH NPT)

SYSTEM

CONTROL VALVE

(NORMALLY

OPEN)

DRAIN OUTLET

CONNECTION

(1/2 INCH NPT)

DRAIN VALVE

(NORMALLY

CLOSED)

PRESSURE SWITCH,

POTTER ELECTRIC PS10-2:

INCREASE  16±1 PSI

DECREASE  8±1 PSI

TUBING

TO SYSTEM

WATER SUPPLY

PRESSURE

GAUGE

FLOW

TUBING

TO SYSTEM

AIR SUPPLY

PRESSURE

GAUGE

SPRING LOADED

CHECK VALVE

SPRING LOADED

CHECK VALVE

FLOW

TEST VALVE

(NORMALLY

CLOSED)

AIR COMPRESSOR

SWITCH TO AIR

COMPRESSOR

WIRING HARNESS

DRY PIPE

FIRE PROTECTION

SYSTEM OUTLET

CONNECTION

(1 or 1-1/2 INCH NPT)

AIR

COMPRESSOR

SWITCH

CUT-IN: 10 PSI

CUT-OUT: 14 PSI

FIGURE 2 

MODEL RCP-1 RESIDENTIAL CONTROL 

MANIFOLD ASSEMBLY

Summary of Contents for RAPID RESPONSE RCP-1

Page 1: ...des the following features Pre wired assembly containing pre programmed control panel system performance gauges and an en closed compressor Pre engineered riser design Supervised system valve system P...

Page 2: ...is document The Model 4004R Household Fire Warning Unit Subassembly Electronic Control installed within the Model RCP 1 cabinet is UL and C UL Listed Maximum Water Pressure 175 psi 12 1 bar Friction L...

Page 3: ...tically maintained at a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Com pressor Switch Air Compressor Fig ure 2 In the standby condition water is prevented from entering the...

Page 4: ...BLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm...

Page 5: ...NORMALLY CLOSED PRESSURE SWITCH POTTER ELECTRIC PS10 2 INCREASE 16 1 PSI DECREASE 8 1 PSI TUBING TO SYSTEM WATER SUPPLY PRESSURE GAUGE FLOW TUBING TO SYSTEM AIR SUPPLY PRESSURE GAUGE SPRING LOADED CHE...

Page 6: ...ill functioning the Electronic Con trol is using battery power to oper ate The cause for loss of AC Power should be determined and correct ed The system is in a normal stand by condition when only the...

Page 7: ...re System or main control valve closure Step 5 Reset the system as soon as possible In Case of Alarm Condition Step 1 Verify that a fire condition ex ists and take appropriate action that is evacuate...

Page 8: ...10k 1 2 W 3 3k 1 2 W 3 3k 3 3k RAC 1 RAC 2 NAC 1 NAC 2 12 18 AWG 1A MAX NOTIFICATION CIRCUIT IDC 2 IDC 1 IDC 4 IDC 3 1 2 W 3 3k SPM 2 SPM 1 R SOLENOID PRE CONNECTED YEL RED TYPICAL 430687 TWIST ON WIR...

Page 9: ...TS LOWER RIGHT HAND CORNER OF ELECTRONIC CONTROL JUMPER SELECTION OPTIONS RELAY CONTACTS SET ALL RELAY JUMPERS TO NORMALLY OPEN JUMPER RIGHT AUXILIARY POWER TERMINALS UPPER RIGHT HAND CORNER OF ELECTR...

Page 10: ...Maximum alarm current is 1A and the maximum distance from the Model RCP 1 Panel to the last de vice is as follows 210 feet for 18 AWG wiring 334 feet for 16 AWG wiring 532 feet for 14 AWG wiring 845...

Page 11: ...se the Flow Test Valve The Water Supply Gauge should drop to a previously noted re sidual pressure and then return to the normal static pressure Step 4 Perform a lamp test by press ing and holding the...

Page 12: ...mber Step 5 Upon completing the program ming check place the PROGRAM SWITCH in the OFF position and then return the Operator Interface card to its normal position NOTICE Exercise care to ensure that a...