TFP480
Page 3 of 12
Tone Alert (Piezo)
•
On trouble conditions, the tone-
alert sounder is on steady to indicate
that a trouble has occurred. It turns
off when ACCEPT SIGNAL KEY is
pressed.
•
On alarm conditions, the tone-alert
pulses until the ACCEPT SIGNAL
KEY is pressed.
Environmental
This equipment operates normally
within the temperature range of 32°F
to 120°F (0°C to 49°C), inclusive. This
equipment operates normally under
non-condensing humidity conditions
up to 93% humidity at 90°F (32°C).
Automatically Controlled System
Air Pressure
10 to 14 psi
System Alarm (Trip/Release) Pres-
sure
8 ± 1 psi
Supervisory High Pressure
16 ± 1 psi
Assembly
The Manifold Assembly (Figure 2) is of
brass and bronze construction.
Trip Ratio
When applying a water delivery cal-
culation program for determining that
the water delivery will not exceed 15
seconds, the trip ratio of the Model
RCP-1 Panel must be entered into the
program. The trip ratio for the Model
RCP-1 Panel is determined by dividing
the available static water supply pres-
sure by 7 psi. The use of 7 psi is based
on the tolerance of the system alarm
trip/release pressure, where 7 psi is the
lowest potential trip pressure. For ex-
ample if the available static water sup-
ply pressure is 30 psi, the trip ratio is 30
divided by 7 (that is, 4.3:1). For an avail-
able 130 psi static water supply, the trip
ratio is 130 divided by 7 (that is, 18.6:1).
Operation
The system is automatically maintained
at a normal system air pressure of 10 to
14 psi (0,7 to 1,0 bar) via the Air Com-
pressor Switch/Air Compressor (Fig-
ure 2). In the standby condition, water
is prevented from entering the system
piping until the Solenoid Valve in the
Manifold Assembly is opened in re-
sponse to the electronic control.
The operation sequence is listed below.
•
The normal standby condition is AC
green light ON.
•
Closure of Main Control Valve, clo-
sure of System Control Valve, or a
high system pressure condition re-
sults in a supervisory condition
(SPM1).
During a Supervisory Condition, the
Yellow SUPERVISORY LED flashes
and the tone-alert sounds steady.
After accepting, the tone-alert si-
lences and the Yellow SUPERVISO-
RY LED stays ON until the condition
clears.
•
Opening of a sprinkler results in a
low air condition of less than nom-
inally 8 psi (0,6 bar) resulting in an
alarm condition ON IDC1, opening of
the Solenoid Valve (RAC1), and op-
eration of alarm notification devices
(NAC1).
During an Alarm Condition, the Red
ALARM LED, corresponding to Zone
or SPM in alarm, flashes and the
tone-alert pulses. After accepting,
the tone-alert silences and the Red
ALARM LED stays ON until the alarm
condition clears.
200
300
500
0,8
0,3
0,4
0,6
0,5
1,0
100
40
100
20
0,2
150
60
80
80
2.0
3.0
4.0
5.0
6.0
8.0
10.0
20.0
FLOW RATE IN LITRES PER MINUTE (LPM)
(1 GPM = 3,785 LPM)
FLOW RATE IN GALLONS PER MINUTE (GPM)
NOMINAL PRESSURE DROP IN BAR
(1 PSI = 0,06895 BAR)
NOMINAL PRESSURE DROP
IN POUNDS PER SQUARE INCH (PSI)
1 INCH (DN25)
1-1/2 INCH (DN40)
400
GRAPH A
MODEL RCP-1 RESIDENTIAL CONTROL PANEL
NOMINAL PRESSURE LOSS VERSUS FLOW