background image

TFP480

Page 3 of 12

Tone Alert (Piezo)

• 

On trouble conditions, the tone-

alert sounder is on steady to indicate 

that a trouble has occurred. It turns 

off when ACCEPT SIGNAL KEY is 

pressed.

• 

On alarm conditions, the tone-alert 

pulses until the ACCEPT SIGNAL 

KEY is pressed. 

Environmental 

This equipment operates normally 

within the temperature range of 32°F 

to 120°F (0°C to 49°C), inclusive. This 

equipment operates normally under 

non-condensing humidity conditions 

up to 93% humidity at 90°F (32°C). 

Automatically Controlled System 

Air Pressure 

10 to 14 psi

System Alarm (Trip/Release) Pres-

sure 

8 ± 1 psi

Supervisory High Pressure 

16 ± 1 psi

Assembly 

The Manifold Assembly (Figure 2) is of 

brass and bronze construction. 

Trip Ratio 

When applying a water delivery cal-

culation program for determining that 

the water delivery will not exceed 15 

seconds, the trip ratio of the Model 

RCP-1 Panel must be entered into the 

program. The trip ratio for the Model 

RCP-1 Panel is determined by dividing 

the available static water supply pres-

sure by 7 psi. The use of 7 psi is based 

on the tolerance of the system alarm 

trip/release pressure, where 7 psi is the 

lowest potential trip pressure. For ex-

ample if the available static water sup-

ply pressure is 30 psi, the trip ratio is 30 

divided by 7 (that is, 4.3:1). For an avail-

able 130 psi static water supply, the trip 

ratio is 130 divided by 7 (that is, 18.6:1). 

Operation 

The system is automatically maintained 

at a normal system air pressure of 10 to 

14 psi (0,7 to 1,0 bar) via the Air Com-

pressor Switch/Air Compressor (Fig-

ure 2). In the standby condition, water 

is prevented from entering the system 

piping until the Solenoid Valve in the 

Manifold Assembly is opened in re-

sponse to the electronic control. 

The operation sequence is listed below.

• 

The normal standby condition is AC 

green light ON. 

• 

Closure of Main Control Valve, clo-

sure of System Control Valve, or a 

high system pressure condition re-

sults in a supervisory condition 

(SPM1). 
During a Supervisory Condition, the 

Yellow SUPERVISORY LED flashes 

and the tone-alert sounds steady.  

After accepting, the tone-alert si-

lences and the Yellow SUPERVISO-

RY LED stays ON until the condition 

clears.

• 

Opening of a sprinkler results in a 

low air condition of less than nom-

inally 8 psi (0,6 bar) resulting in an 

alarm condition ON IDC1, opening of 

the Solenoid Valve (RAC1), and op-

eration of alarm notification devices 

(NAC1). 
During an Alarm Condition, the Red 

ALARM LED, corresponding to Zone 

or SPM in alarm, flashes and the 

tone-alert pulses. After accepting, 

the tone-alert silences and the Red 

ALARM LED stays ON until the alarm 

condition clears.

200

300

500

0,8

0,3

0,4

0,6

0,5

1,0

100

40

100

20

0,2

150

60

80

80

2.0

3.0

4.0

5.0

6.0

8.0

10.0

20.0

FLOW RATE IN LITRES PER MINUTE (LPM)

(1 GPM = 3,785 LPM)

FLOW RATE IN GALLONS PER MINUTE (GPM)

NOMINAL PRESSURE DROP IN BAR

(1 PSI = 0,06895 BAR)

NOMINAL PRESSURE DROP

IN POUNDS PER SQUARE INCH (PSI)

1 INCH (DN25)

1-1/2 INCH (DN40)

400

GRAPH A  

MODEL RCP-1 RESIDENTIAL CONTROL PANEL  

NOMINAL PRESSURE LOSS VERSUS FLOW

Summary of Contents for RAPID RESPONSE RCP-1

Page 1: ...des the following features Pre wired assembly containing pre programmed control panel system performance gauges and an en closed compressor Pre engineered riser design Supervised system valve system P...

Page 2: ...is document The Model 4004R Household Fire Warning Unit Subassembly Electronic Control installed within the Model RCP 1 cabinet is UL and C UL Listed Maximum Water Pressure 175 psi 12 1 bar Friction L...

Page 3: ...tically maintained at a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Com pressor Switch Air Compressor Fig ure 2 In the standby condition water is prevented from entering the...

Page 4: ...BLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm...

Page 5: ...NORMALLY CLOSED PRESSURE SWITCH POTTER ELECTRIC PS10 2 INCREASE 16 1 PSI DECREASE 8 1 PSI TUBING TO SYSTEM WATER SUPPLY PRESSURE GAUGE FLOW TUBING TO SYSTEM AIR SUPPLY PRESSURE GAUGE SPRING LOADED CHE...

Page 6: ...ill functioning the Electronic Con trol is using battery power to oper ate The cause for loss of AC Power should be determined and correct ed The system is in a normal stand by condition when only the...

Page 7: ...re System or main control valve closure Step 5 Reset the system as soon as possible In Case of Alarm Condition Step 1 Verify that a fire condition ex ists and take appropriate action that is evacuate...

Page 8: ...10k 1 2 W 3 3k 1 2 W 3 3k 3 3k RAC 1 RAC 2 NAC 1 NAC 2 12 18 AWG 1A MAX NOTIFICATION CIRCUIT IDC 2 IDC 1 IDC 4 IDC 3 1 2 W 3 3k SPM 2 SPM 1 R SOLENOID PRE CONNECTED YEL RED TYPICAL 430687 TWIST ON WIR...

Page 9: ...TS LOWER RIGHT HAND CORNER OF ELECTRONIC CONTROL JUMPER SELECTION OPTIONS RELAY CONTACTS SET ALL RELAY JUMPERS TO NORMALLY OPEN JUMPER RIGHT AUXILIARY POWER TERMINALS UPPER RIGHT HAND CORNER OF ELECTR...

Page 10: ...Maximum alarm current is 1A and the maximum distance from the Model RCP 1 Panel to the last de vice is as follows 210 feet for 18 AWG wiring 334 feet for 16 AWG wiring 532 feet for 14 AWG wiring 845...

Page 11: ...se the Flow Test Valve The Water Supply Gauge should drop to a previously noted re sidual pressure and then return to the normal static pressure Step 4 Perform a lamp test by press ing and holding the...

Page 12: ...mber Step 5 Upon completing the program ming check place the PROGRAM SWITCH in the OFF position and then return the Operator Interface card to its normal position NOTICE Exercise care to ensure that a...

Reviews: