TFP480

Page 9 of 12

TBL 

TROUBLE RELAY (SELECT NORMALLY

OPEN OR NORMALLY CLOSED)

RELAY #2 (SELECT NORMALLY

OPEN OR NORMALLY CLOSED)

RELAY #3 (SELECT NORMALLY

OPEN OR NORMALLY CLOSED)

ALARM

SUPERVISORY

RELAY #2 JUMPER
TROUBLE RELAY JUMPER

RELAY #3 JUMPER

#2

#3

JUMPER LEFT

NORMALLY CLOSED

JUMPER RIGHT

NORMALLY OPEN

JUMPERS TO SELECT

NORMALLY OPEN OR

CLOSED CONTACTS

LOWER RIGHT-HAND CORNER

OF ELECTRONIC CONTROL

JUMPER SELECTION OPTIONS

RELAY

CONTACTS

SET ALL

RELAY JUMPERS TO

NORMALLY OPEN

(JUMPER RIGHT)

+ -

AUXILIARY

POWER

TERMINALS

UPPER

RIGHT-HAND

CORNER OF

ELECTRONIC

CONTROL

LOWER

RIGHT-HAND

CORNER OF

ELECTRONIC

CONTROL

ADD

JUMPERS AS

SHOWN

REMOTE SIGNAL:

24 VDC, 0.25 AMP

MAXIMUM (LOCATE

CONSPICUOUSLY

IN LIVING SPACE;

YELLOW LIGHT

RECOMMENDED)

NOTICE:

FOR ON-SITE

REMOTE

SUPERVISORY/

TROUBLE SIGNAL

CONNECTIONS

ONLY

FIGURE 5  

ELECTRONIC CONTROL 

OFF-SITE REMOTE RELAYS

FIGURE 6  

ELECTRONIC CONTROL 

ON-SITE REMOTE SIGNAL

Summary of Contents for RAPID RESPONSE RCP-1

Page 1: ...des the following features Pre wired assembly containing pre programmed control panel system performance gauges and an en closed compressor Pre engineered riser design Supervised system valve system P...

Page 2: ...is document The Model 4004R Household Fire Warning Unit Subassembly Electronic Control installed within the Model RCP 1 cabinet is UL and C UL Listed Maximum Water Pressure 175 psi 12 1 bar Friction L...

Page 3: ...tically maintained at a normal system air pressure of 10 to 14 psi 0 7 to 1 0 bar via the Air Com pressor Switch Air Compressor Fig ure 2 In the standby condition water is prevented from entering the...

Page 4: ...BLY AIR PRESSURE CONTROL Always consult local jurisdictions for water supply criteria and requirements Nominal Weight 95 LBS 43 kg MOUNTING BRACKETS 2 7 8 73 mm ELECTRONIC CONTROL 1 3 4 45 mm 5 127 mm...

Page 5: ...NORMALLY CLOSED PRESSURE SWITCH POTTER ELECTRIC PS10 2 INCREASE 16 1 PSI DECREASE 8 1 PSI TUBING TO SYSTEM WATER SUPPLY PRESSURE GAUGE FLOW TUBING TO SYSTEM AIR SUPPLY PRESSURE GAUGE SPRING LOADED CHE...

Page 6: ...ill functioning the Electronic Con trol is using battery power to oper ate The cause for loss of AC Power should be determined and correct ed The system is in a normal stand by condition when only the...

Page 7: ...re System or main control valve closure Step 5 Reset the system as soon as possible In Case of Alarm Condition Step 1 Verify that a fire condition ex ists and take appropriate action that is evacuate...

Page 8: ...10k 1 2 W 3 3k 1 2 W 3 3k 3 3k RAC 1 RAC 2 NAC 1 NAC 2 12 18 AWG 1A MAX NOTIFICATION CIRCUIT IDC 2 IDC 1 IDC 4 IDC 3 1 2 W 3 3k SPM 2 SPM 1 R SOLENOID PRE CONNECTED YEL RED TYPICAL 430687 TWIST ON WIR...

Page 9: ...TS LOWER RIGHT HAND CORNER OF ELECTRONIC CONTROL JUMPER SELECTION OPTIONS RELAY CONTACTS SET ALL RELAY JUMPERS TO NORMALLY OPEN JUMPER RIGHT AUXILIARY POWER TERMINALS UPPER RIGHT HAND CORNER OF ELECTR...

Page 10: ...Maximum alarm current is 1A and the maximum distance from the Model RCP 1 Panel to the last de vice is as follows 210 feet for 18 AWG wiring 334 feet for 16 AWG wiring 532 feet for 14 AWG wiring 845...

Page 11: ...se the Flow Test Valve The Water Supply Gauge should drop to a previously noted re sidual pressure and then return to the normal static pressure Step 4 Perform a lamp test by press ing and holding the...

Page 12: ...mber Step 5 Upon completing the program ming check place the PROGRAM SWITCH in the OFF position and then return the Operator Interface card to its normal position NOTICE Exercise care to ensure that a...

Reviews: