capacity and not less than a total free area of 10 square inches (64.5 cm²). If
ventilation openings shall be at floor level and are in a sidewall, there shall be
at least two openings. The bottom of the openings shall be at floor level and
the upper edge no more that 5 inches (127 mm) above the floor. The
openings shall be equally sized, spaced at 180 degrees (3.14 rad) and
unobstructed.
3.
Every opening shall have minimum dimensions so as to permit the entrance
of 1/8 inch (3.2 mm) diameter rod.
LP Gas Connection
Procedure for LP Gas Cylinder Connection (20 lbs)
1. Turn Hand Wheel on cylinder clockwise until it stops to ensure the Cylinder Valve is fully
closed.
2. Turn the burner knob to the OFF position.
3. Connect the ½” NPT x ½” Flare brass coupling (coupling not supplied with product) to
the end of the gas line on the product.
4. Connect the ½” Flare end of the hose to the brass coupling on the grill using a ¾” open
wrench. Do not apply pipe sealant.
5. Connect the regulator to the LP cylinder. Do not use any tools. Hand-tighten the
regulator.
6. Check for leaks using a soapy water solution.
7. See figure above for a typical LP gas hook up.
8. To disconnect after use, turn the burner knob to the OFF position. Close the Cylinder
Valve by turning the Hand Wheel counter-clockwise until it stops.
9.
Disconnect the regulator from the LP cylinder after use.