Setting
Setting by manual bridging (shorting)
42
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Setting output 2 as a voltage output
NOTE
If output 2 is set as a voltage output, the closer teach-in point corresponds to limit
value 1 (0 V) and the teach-in point further away to limit value 2 (10 V).
Out2: set
Current output
Voltage output
Switch only:
inverted Out1
U
B
/T2 > 2 s
7 s
LED YE 1 × 1 Hz
U
B
/T2 >
8 s
16 s
LED YE 2 × 1 Hz
U
B
/T2 >
14 s
19 s
LED YE 3 × 1 Hz
OK
LED GN
1.5 s × 5 Hz
Normal
operation
Fig. 37: Setting output 2
Bridge pin 1 (BN) with pin 5 (GY) for 8…13 s.
Set limit values for the window function.
a
Output 2 is set successfully as a voltage output if the green LED flashes for 1.5 s at a
frequency of 5 Hz.