V2.0 | 2021/06
45
Window function – setting the switching range
Window function
Out2
Out1
GND/T1 > 8 s
13 s
LED GN 2 × 1 Hz
GND/T1 > 8 s
13 s
LED YE 2 × 1 Hz
Measure and save
SP1
Fail
LED GN/YE
1.5 s × 5 Hz
GND/T1 > 2 s
7 s
LED GN 1 × 1 Hz
GND/T1 > 2 s
7 s
LED GN 1 × 2 Hz
Measure and save
SP2
OK
LED GN
1.5 s × 5 Hz
Normal
operation
U
B
/T2 > 2 s
LED YE
1 × 8 Hz
Cancel
Fig. 40: Window function – setting the switching range
Position the object for switching point 1.
Select the switching output.
Store switching point 1: Press and hold down pushbutton 1 for 8…13 s.
Position the object for switching point 2.
Store switching point 2: Press and hold down pushbutton 1 for 2…7 s.
a
The switching points have been successfully taught if the green LED flashes for 1.5 s at a
frequency of 5 Hz.