V2.0 | 2021/06
33
Setting output 2 as a current output
NOTE
If output 2 is set as a voltage output, the closer teach-in point corresponds to limit
value 1 (0 V) and the teach-in point further away to limit value 2 (10 V).
Out2: set
Current output
Voltage output
Switch only:
inverted Out1
U
B
/T2 > 2 s
7 s
LED YE 1 × 1 Hz
U
B
/T2 >
8 s
16 s
LED YE 2 × 1 Hz
U
B
/T2 >
14 s
19 s
LED YE 3 × 1 Hz
OK
LED GN
1.5 s × 5 Hz
Normal
operation
Fig. 28: Setting output 2
Connect the TX1-Q20L60 teach adapter between the sensor and the connection cable.
Press and hold down the pushbutton on the adapter for 8…13 s to U
B
.
Set limit values for the window function.
a
Output 2 is set successfully as a voltage output if the green LED flashes for 1.5 s at a
frequency of 5 Hz.