V01.00 | 2020/11
13
Name
Index
hex.
(dec.)
Sub-
index
hex.
(dec.)
Subindex
access
supported
Access Byte.
Bit-
Offset
Bit
length
Data Type Value Default Description
Measurement
quantity
0x54
(84)
0x1
(1)
False
read/
write
0.0
8
UInteger 0…5
0
0
Distance
1
Distance %
2
Level
3
Level %
4
Volume
5
Volume %
Length unit
0x54
(84)
0x2
(2)
False
read/
write
1.0
8
UInteger 0…3
1
0
Millimeters
1
Meters
2
Inches
3
Feet
Volume unit
0x54
(84)
0x3
(3)
False
read/
write
2.0
8
UInteger 0…4
0
0
Liters
1
Cubic meters
2
Cubic inches
3
Cubic feet
4
Gallons
Display
actualization
rate
0x55
(85)
0x0
(0)
True
read/
write
0.0
8
UInteger 0…3
0
Display update period
0
50 ms
1
200 ms
2
600 ms
3
Display off
Output 1:
Errorstate
0x56
(86)
0x0
(0)
True
read/
write
0.0
8
UInteger 0…1
0
State of output switch 1 in
case of error
0
Switch inactive
1
Switch active
Output 2:
Errorstate
0x57
(87)
0x0
(0)
True
read/
write
0.0
8
UInteger 0…1
0
State of output switch 2 in
case of error
0
Switch inactive
1
Switch active
Virtual FH
0x59
(89)
0x1
(1)
False
read/
write
0.0
28
Integer
-1999
9999
…
99999
999
50000 Measured value ÷ 10000 =
Value in unit
The values change if the
unit is adjusted.
Virtual FL
0x59
(89)
0x2
(2)
False
read/
write
4.0
28
Integer
-1999
9999
…
99999
999
75000 Measured value ÷ 10000 =
Value in unit
The values change if the
unit is adjusted.