Setting
Settable functions and properties
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V02.00 | 2022/08 | 19
9
Setting
9.1
Settable functions and properties
The three front touchpads (ENTER, MODE, SET) enable the user to set all the essential functions
and properties directly on the device via the menu guidance. It is also possible to configure the
device via the IO-Link interface (see IO-Link parameter manual).
Setting options – via touchpads and IO-Link interface
The following functions and properties can be set and used both in standard I/O mode as well
as in IO-Link mode.
n
Locking/unlocking touchpads
n
FLOW switching point: Quick-Teach
n
FLOW switching point: MAX/MIN teach-in
n
Indicated range: MAX/MIN teach-in
n
TEMP switching point
n
Advanced settings: Reset to the previous settings (Pre-Settings)
n
Advanced settings: Reset to factory settings
n
Advanced settings: Output FLOW: NO/NC changeover
n
Advanced settings: Output TEMP: NO/NC changeover
Other setting options — only via IO-Link
Additional functions and properties can also be set via the IO-Link interface.
n
OUT1 output configuration for SIO mode: PNP/NPN, automatic detection on/off
n
OUT2 output configuration for SIO mode: PNP/NPN, automatic detection on/off
n
Setting display units for IO-Link mode: metric, imperial
n
Lock data storage on IO-Link master
n
Fully lock user interface (display and touchpads locked)
n
Lock parameters (parameters are displayed but cannot be changed)
Factory settings
n
Medium: water
n
Flow switching point: 70 % of the indicated range
n
MAX/MIN mode
n
MAX value: maximum
n
MIN value: minimum
n
Temperature switching point: 60 °C
n
Output function Out 1: NO contact
n
Output function Out 2: NO contact
n
Automatic detection function on
Automatic detection function
The Automatic detection function supports the error-free configuration of the sensor for con-
necting to the remote I/O environment: The sensor automatically activates the output signal
that corresponds to the signal type of the connected input card. The Automatic detection func-
tion is active by default. The output can also be set selectively as required via the IO-Link inter-
face.