Installing
5.1
General installation instructions
For optimal monitoring, mount the sensor such that the probe rod is fully immersed in
the medium.
If the medium flows in a horizontal direction and may contain deposits or trapped gas
(e.g. air bubbles): Mount the sensor e.g. laterally.
Fig. 7: Lateral mounting
If the medium flows in a horizontal direction and the flow channel is not completely filled
with the medium: Mount the sensor e.g. below the flow.
Fig. 8: Mounting below the flow
If the medium flows in a vertical direction: Mount the sensor only in risers.
A minimum distance from potential interference variables (pumps, valves, flow rectifiers,
pipe bends, changes in the cross section) must be maintained.
d
b
a
a ≥ 10 x d
b ≥ 5 x d
Fig. 9: Minimum distances to interference variables
Prevent the tip of the probe rod coming into contact with the opposite side of the flow
channel inner wall.