Setting
Setting via touchpads
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V02.00 | 2022/08 | 20
9.2
Setting via touchpads
9.2.1
Locking and unlocking the device
To prevent accidental entries, the touch pads are automatically locked after switching on and
after 5 minutes without being pressed (after 30 minutes in setting mode). If the key lock is
activated, teach-in procedures cannot be initiated and parameters cannot be changed.
Locking the device (LOC)
Press and hold [MODE] and [SET] for 3 s.
a
The LOC LED first flashes and then turns a constant yellow.
Unlocking the device (uLOC)
LED indicator bar
Press and hold [ENTER] until all the LEDs in the LED bar turn
green and the LED bar briefly flashes green twice.
2x
Swipe across each the touchpads with your finger — in the
order [MODE], [ENTER], [SET] until all the LEDs (3 × 3) in the
LED bar are flashing green.
Release the touchpads.
a
The LOC LED flashes first and then goes out.
9.2.2
Setting options
The user can set the main device functions directly on the device via the touchpads [ENTER],
[MODE] and [SET]:
Setting options — devices with switching output for flow monitoring
1
FLOW switching point:
Quick-Teach
Quick-Teach: Current flow speed is directly taught in as the FLOW
switching point
2
FLOW switching point:
MAX/MIN teach-in
MAX/MIN teach-in: Set the FLOW switching point as a percentage
of a configurable MAX/MIN indicated range
3
Indicated range: MAX/
MIN teach-in
MAX/MIN teach-in: Teach in the upper and lower limit values for
the flow monitoring indicated range
4
TEMP switching point Set the TEMP switching point in increments of 2 °C from
-40…+180 °C
5
Advanced
settings
Reset to last setting
Reset to factory setting
Change FLOW output over to NO/NC
Change TEMP output over to NO/NC