Instructions for Use

FS100…L…-2UPN8

Flow Sensors

Summary of Contents for FS100 L Series

Page 1: ...Your Global Automation Partner Instructions for Use FS100 L 2UPN8 Flow Sensors...

Page 2: ...4 1 1 Display and control elements 9 4 2 Properties and features 9 4 3 Operating and display functions 9 4 4 Operating principle 9 4 5 Functions and operating modes 9 4 5 1 Flow monitoring 9 4 5 2 Te...

Page 3: ...Teach setting the current flow speed as the switching point 22 9 2 4 MAX MIN teach in setting the switching point for flow 22 9 2 5 MAX MIN teach in setting the indicated range for flow 23 9 2 6 Setti...

Page 4: ...Contents Hans Turck GmbH Co KG T 49 208 4952 0 more turck com www turck com V02 00 2022 08 4...

Page 5: ...not avoided WARNING WARNING indicates a dangerous situation with medium risk of death or severe in jury if not avoided CAUTION CAUTION indicates a dangerous situation of medium risk which may result...

Page 6: ...livery includes n Compact flow sensor n Thread adapter for process connection not with FS100 00 n Two seals not on devices with NPT and R threads n Quick Start Guide 2 3 Turck service Turck supports y...

Page 7: ...protecting pumps from running dry Based on the calorimetric principle the devices can also be used to measure the media temperature The devices may only be used as described in these instructions Any...

Page 8: ...verview The overview shows example dimension drawings of the compact flow sensors Plug in devices 22 L1 96 4 38 27 7 3 M12 x 1 9 5 L 41 3 M18 x 1 5 11 11 37 14 5 G1 4 M18 x 1 5 22 L1 96 4 38 27 M12 x...

Page 9: ...switching status and device status 4 4 Operating principle The flow sensors operate calorimetrically The function is based on the thermo dynamic prin ciple When the medium is flowing thermal energy i...

Page 10: ...master When the port is configured in IO Link mode bidirectional IO Link communication takes place between the IO Link master and the device To make this possible the device is integrated via an IO L...

Page 11: ...ss connection G1 4 27 11 37 14 5 G1 2 M18 x 1 5 FAA 80 1 4571 100001988 Screw in adapter for immersion sensors from the FS FP product series material stainless steel 1 4571 316Ti process connection G1...

Page 12: ...rally Fig 7 Lateral mounting If the medium flows in a horizontal direction and the flow channel is not completely filled with the medium Mount the sensor e g below the flow Fig 8 Mounting below the fl...

Page 13: ...ensor M18 1 5 coupling nut with the screw in adapter For a standard flow range 3 300 cm s The probe rod can be installed in the medium independent of the flow direction range of 360 For an extended fl...

Page 14: ...plug in devices Connect the connection cable coupling to the sensor connector Connect the connection cable to the power source as shown in the wiring diagram 6 1 1 Wiring diagram 4 3 1 2 param NO NC...

Page 15: ...is phase the LED indicator bar flashes yellow and the two output LEDs FLOW and TEMP are switched off The warm up phase is deemed to be complete n If the period of 30 seconds that is allotted for the w...

Page 16: ...operational Green flashing IO Link communication active inverted Ton 900 ms Toff 100 ms FLOW Yellow NO switching output Switching point exceeded HIGH level NC switching output Switching point undersho...

Page 17: ...m the FLOW switching point are indicated in 9 1 increments by green LEDs Green LEDs to the left of the yellow switching point LED indicate that the switching point is being undershot green LEDs to the...

Page 18: ...T Yellow flashing Flow speed above the indicated range Yellow flashing Flow speed below the indicated range Yellow flashing Media temperature above the indicated range Yellow flashing Media temperatur...

Page 19: ...setting options only via IO Link Additional functions and properties can also be set via the IO Link interface n OUT1 output configuration for SIO mode PNP NPN automatic detection on off n OUT2 outpu...

Page 20: ...finger in the order MODE ENTER SET until all the LEDs 3 3 in the LED bar are flashing green Release the touchpads a The LOC LED flashes first and then goes out 9 2 2 Setting options The user can set t...

Page 21: ...wer ON Check LED tHeatUp tfix t Flow Flow acc small Holding time no yes DeltaFlow Monitoring simultaneously Cancel Settings Advanced Settings w 5 Flow Flow MAX MIN gap MAX teach MIN teach Set MIN 3 s...

Page 22: ...is taught in as the switching point 3 Optional Change the switching point incrementally by 0 5 Increase the switching point incrementally by 0 5 of the measuring range end value Press SET Reduce the s...

Page 23: ...reen Once the LED bar is flashing green the system has sta bilized Press SET for 3 s until only LED 11 is a constant green Store the upper limit value Press ENTER a LED bar briefly flashes green twice...

Page 24: ...ching point LED first flashes yellow and then changes to a constant yellow again Increase the switching point in increments of 2 C Press SET Reduce the switching point in increments of 2 C Press MODE...

Page 25: ...ting Press SET for at least 3 s until LEDs 11 6 quickly flash green one after the other Save settings Press ENTER LED bar briefly flashes green twice The next menu appears 2x Reset to factory settings...

Page 26: ...NC LEDs 5 7 off NO LEDs 4 and 8 flash green Change the output function from NO to NC Press and hold SET for at least 3 s until LEDs 4 and 8 first flash green quickly and then return to a constant gree...

Page 27: ...LEDs 4 8 are green NC LEDs 4 to 8 flash green Change output function from NC to NO Press and hold SET for at least 3 s until green LEDs 4 to 8 first flash green quickly and then return to a constant g...

Page 28: ...vice does not function as expected first check whether there is any ambient interfer ence If there is no ambient interference check the connections of the device for faults If no faults are identified...

Page 29: ...oned if it is faulty Observe our return acceptance conditions when returning the device to Turck 12 1 Returning devices Returns to Turck can only be accepted if the device has been equipped with a Dec...

Page 30: ...50 mA Short circuit protection Yes cyclic Overload protection Yes Reverse polarity protection Yes Standby delay time min 18 s IO Link IO Link specification V1 1 IO Link port type Class A Transmission...

Page 31: ...com www turck com V02 00 2022 08 31 Technical data Type of protection IP66 IP67 IP69K MTF 120 years acc to SN 29500 Ed 99 40 C Display functions LEDs indicate the status of the power supply outputs a...

Page 32: ...6G 1B5 www turck ca China Turck Tianjin Sensor Co Ltd 18 4th Xinghuazhi Road Xiqing Economic Development Area 300381 Tianjin www turck com cn Czech Republic TURCK s r o Na Brne 2065 CZ 500 06 Hradec K...

Page 33: ...d TURCK sp z o o Wroclawska 115 PL 45 836 Opole www turck pl Romania Turck Automation Romania SRL Str Siriului nr 6 8 Sector 1 RO 014354 Bucuresti www turck ro Russian Federation TURCK RUS OOO 2 nd Pr...

Page 34: ...Over 30 subsidiaries and 60 representations worldwide www turck com 100002085 2022 08 100002085...