D301239 1013 - BL67 AIDA PROFINET
4-37
Parameterization
BL67-1SSI
1
3
Data bits
0 = 7
A
– The number of data bits is 7.
1 + 8
– The number of data bits is 8.
Table 4-26:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
0
4 to 0
reserved
5
Sensor
data cable
test
0 = activate
A
– ZERO test of data cable.
1 = deactivate
– After the last valid bit, a ZERO test of the
data cable is not carried out.
7.6
reserved
1
3 to 0
Number of
invalid bits
(LSB)
0000 to 1111
Number of invalid bits on the LSB side of the
position value supplied by the SSI encoder.
The meaningful word width of the position
value transferred to the module bus master is
as follows:
SSI_FRAME_LEN -INVALID_BITS_MSB-
INVALID_BITS_LSB.
The invalid bits on the LSB side are removed
by shifting the position value to the right,
starting with the LSB.
(Default 0 bit = 0×0).
INVALID_BIINVALID_BITS_LSB must
always be less than SSI_FRAME_LEN.
Table 4-25:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
Summary of Contents for BL67-GW-PN-AC
Page 1: ...USER MANUAL PROFINET AIDA gateway BL67 GW PN AC...
Page 6: ...D301239 1013 BL67 AIDA PROFINET iv...
Page 20: ...PROFINET D301239 1013 BL67 AIDA PROFINET 3 4...
Page 66: ...Technical features D301239 1013 BL67 AIDA PROFINET 4 46...
Page 94: ...Guidelines for station planning D301239 1013 BL67 AIDA PROFINET 6 6...
Page 112: ...Mounting and mounting instructions D301239 1013 BL67 AIDA PROFINET 8 10...
Page 116: ...Appendix D301239 1013 BL67 AIDA PROFINET 9 4...