D301239 1013 - BL67 AIDA PROFINET
4-25
Parameterization
BL67-4AI-TC
(1 byte parameters per channel)
BL67-4AI-V/I (1 byte parameters per channel)
Table 4-14:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
0 to 3
0
reserved
1
Value representation
0 = Integer (15 bit + sign)
A
1 = 12 bit (left-justified)
2 Diagnosis
0
=
release
A
1 = block
3 Channel
0
=
activate
A
1 = deactivate
7 to 4
Element
0000 = Type K, -270...1370 °C
A
0001 = Type B, +100....1820 °C
0010 = Type E, -270...1000 °C
0011 = Type J, -210...1200 °C
0100 = Type N, -270...1300 °C
0101 = Type R, -50...1760 °C
0110 = Type S, -50...1540 °C
0111 = Type T, -270...400 °C
1000 = ± 50 mV
1001 = ± 100 mV
1010 = ± 500 mV
1011 = ± 1000 mV
1100 = Type K, -454…2498 °F
1101 = Type J, -346...2192 °F
1110 = Type C, 0...2315°C
11111 = Type G, 0...2315°C
Table 4-15:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
0 to 3
0
range
0 = 0...10 V/ 0...20 mA
A
1 = -10...+10 V/ 4...20 mA
1
Value representation
0 = Integer (15 bit + sign)
A
1 = 12 bit (left-justified)
2 Diagnosis
0
=
release
A
1 = block
3 Channel
0
=
activate
A
1 = deactivate
4
Operation mode
0 = voltage
A
1 = current
Summary of Contents for BL67-GW-PN-AC
Page 1: ...USER MANUAL PROFINET AIDA gateway BL67 GW PN AC...
Page 6: ...D301239 1013 BL67 AIDA PROFINET iv...
Page 20: ...PROFINET D301239 1013 BL67 AIDA PROFINET 3 4...
Page 66: ...Technical features D301239 1013 BL67 AIDA PROFINET 4 46...
Page 94: ...Guidelines for station planning D301239 1013 BL67 AIDA PROFINET 6 6...
Page 112: ...Mounting and mounting instructions D301239 1013 BL67 AIDA PROFINET 8 10...
Page 116: ...Appendix D301239 1013 BL67 AIDA PROFINET 9 4...