D301239 1013 - BL67 AIDA PROFINET
4-21
Parameterization
4.11.3
I/O-module-parameters
Digital input modules
BL67-4DI-PD
BL67-8DI-PD
Table 4-8:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
0
0 to 3
Input filter channel
0 to 3
0 = deactivate
A
– input filter: 0.25 ms
1 = activate:
– input filter: 2.5 ms
1
0 to 3
digital input channel 0 to
3
0 = normal
A
– input signal not inverted
1 = inverted:
– input signal inverted, conversion of the
effective signal direction for sensors
2
0, 1
operation mode group 1/
2
0 = normal
– Input is evaluated as input
1 = open-circuit monitoring
– Module works in the mode for open-circuit
monitoring.
→
group 1 (channel 0 and 2) or
2 (channel 1 and 3)
Table 4-9:
Module parame-
ters
A
default
setting
Byte Bit
Parameter
name
Value
–
Meaning
0
0 to 7
Input filter channel
0 to 7
0 = deactivate
A
– input filter: 0.25 ms
1 = activate:
– input filter: 2.5 ms
1
0 to 7
digital input channel 0 to
7
0 = normal
A
– input signal not inverted
1 = inverted:
– input signal inverted, conversion of the
effective signal direction for sensors
2
0, 1, 2, 3
operation mode group 1/
4
0 = normal
– Input is evaluated as input
1 = open-circuit monitoring
– Module works in the mode for open-circuit
monitoring.
→
group:
1 (channel 0/4), 2 (channel 1/5),
3 (channel 2/6), 4 (channel 3/7)
Summary of Contents for BL67-GW-PN-AC
Page 1: ...USER MANUAL PROFINET AIDA gateway BL67 GW PN AC...
Page 6: ...D301239 1013 BL67 AIDA PROFINET iv...
Page 20: ...PROFINET D301239 1013 BL67 AIDA PROFINET 3 4...
Page 66: ...Technical features D301239 1013 BL67 AIDA PROFINET 4 46...
Page 94: ...Guidelines for station planning D301239 1013 BL67 AIDA PROFINET 6 6...
Page 112: ...Mounting and mounting instructions D301239 1013 BL67 AIDA PROFINET 8 10...
Page 116: ...Appendix D301239 1013 BL67 AIDA PROFINET 9 4...