D301239 1013 - BL67 AIDA PROFINET
4-17
Parameterization
4.11
Parameterization
4.11.1
Gateway parameters
The BL67-gateways for PROFINET occupy 4 parameter bytes.
Description of the gateway-parameters
Table 4-7:
gateway
parameters
Byte Bit parameters
Value
Meaning
A
default
setting
0
Byte 0
bit 0, bit 1
Output behavior if one module is missing
00
output 0
A
The gateway switches the outputs of modules to "0".
No error information is transmitted. No error
information is transmitted.
01
output substitute
value
The gateway switches the outputs of all modules to
"0" (with the exception of analog output modules).
Error information is transmitted to the analog output
modules. Depending on their configuration, these
modules set their outputs either to "0" or to a default
value, or to maintain the original values. The non-
configured analog output modules set their outputs
to "0".
10
hold current value The gateway maintains the actual output settings of
all modules (with the exception of analog output
modules). Error information is transmitted to the
analog output modules. Depending on their
configuration, these modules set their outputs either
to "0" or to a default value, or to maintain the original
values. The non-configured analog output modules
set their outputs to "0".
11
exchange process
data
The gateway carries on exchanging process data with
the other module bus stations. No error information is
transmitted.
bit 2, bit 3
Output behavior if one module is wrong
00
output 0
A
The gateway switches the outputs of modules to "0".
No error information is transmitted. No error
information is transmitted.
01
output substitute
value
The gateway switches the outputs of all modules to
"0" (with the exception of analog output modules).
Error information is transmitted to the analog output
modules. Depending on their configuration, these
modules set their outputs either to "0" or to a default
value, or to maintain the original values. The non-
configured analog output modules set their outputs
to "0".
Summary of Contents for BL67-GW-PN-AC
Page 1: ...USER MANUAL PROFINET AIDA gateway BL67 GW PN AC...
Page 6: ...D301239 1013 BL67 AIDA PROFINET iv...
Page 20: ...PROFINET D301239 1013 BL67 AIDA PROFINET 3 4...
Page 66: ...Technical features D301239 1013 BL67 AIDA PROFINET 4 46...
Page 94: ...Guidelines for station planning D301239 1013 BL67 AIDA PROFINET 6 6...
Page 112: ...Mounting and mounting instructions D301239 1013 BL67 AIDA PROFINET 8 10...
Page 116: ...Appendix D301239 1013 BL67 AIDA PROFINET 9 4...