920.1020.15
33
o
Fire rated power operated doors must close and latch during a fire alarm condition.
Ensure proper procedures have been followed to allow a main power disconnect
during a fire alarm condition. Always check to ensure compliance to local building
codes.
§
Upon job completion, always perform a functional test to ensure that the
door(s) close and latch following a power loss.
o
Other hardware may be required to complete the installation. For example, for pairs
of doors, if an Astragal is installed, a mechanical door coordinator may be required
to ensure a proper coordinated closing during a power loss.
o
Only fire rated hardware shall be used on a fire rated door & frame assembly.
o
Ensure the Tucker SW10/19 that is being installed has the proper fire rated label
applied to the header.