30
5.6.3 Meter Address Setting
5.6.3.1 Single Phase Meter
The setting methods for single-phase meter is as follows:
①
Power on the meter to the display interface and long press “
→
”button to enter meter
switching interface, select
and wait for 2s to enter meter address page
automatically.
②
After entering the address page, please press “
→
” to set meter address according to
the system type into 1 or 2.
③
After the address is set, the interface will jump to the initial display interface and no
further operation is required to start the meter.
5.6.3.2 Three Phase Meter
The setting methods for three-phase meter is as follows.
①
Power on the meter and enter the “Measure display” interface, then press “SET”
button twice for entering password 701.
②
Press “
→
” button once to adjust the value of the first digit, one increment per button
pressing.
③
Pressing “SET” button once to shift to the second digit, same methods to adjust value
as for the first digit, then adjust the third digit in a same way, set the default password
into 701.
Note
!
If CT solution is adopted,
please ignore this section.