6.
Electrical connection
Note
All installation work must comply with the specifications of
the Authority Having Jurisdiction (AHJ).
Connection cables carry life-threatening voltage.
Ø
Do not work under voltage.
Ø
Before connecting, check battery cables to ensure that they
are not electrically live.
Ø
Before connecting, check DC link voltage cables to ensure
that they are not electrically live.
Danger of fire
Ø
Observe the installation regulations of the installation site.
Ø
Fuse the battery connection with max. 350 ADC at all poles.
Ø
Fuse the DC link with max. 20 ADC at all poles.
Interchanged polarity destroys DC-DC modules.
Ø
Maintain polarity.
Abrupt connection of the DC link voltage can destroy DC-
DC modules.
Ø
Slowly increase the DC link voltage of 0 V to maximum volt-
age (ramp > 1 s).
Abrupt connection of the battery voltage can destroy the
DC-DC module.
Ø
Pre-charge battery connection parts of the DC-DC module
to current battery voltage.
6.1
Establishing electrical connection
Condition
■
Battery is fully discharged for all connection work.
6
‐
8
Electrical connection
2020-07-01
A67-0140-00.BKen-0
01-05
DANGER
DANGER
NOTICE
NOTICE
NOTICE
Summary of Contents for TruConvert DC 1000 Series
Page 1: ...Operator s manual TruConvert DC series 1000 TruConvert System Control TruConvert Modular...
Page 2: ......
Page 6: ...II Good to know 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 36: ...3 12 Technical data dependent on device variant overview 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 38: ...7 Ethernet 4 10 8 RS 485 4 11 4 2 Interfaces 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 40: ...Fig 4 3 4 4 Protective earth TruConvert DC series 1000 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 48: ...4 12 RS 485 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 54: ...5 6 CSA certification 2020 07 01 A67 0140 00 BKen 0 01 05...
Page 106: ...16 State diagram State machine Fig 7 19 7 38 State diagram 2020 07 01 A67 0140 00 BKen 0 01 05...