background image

EN

15

dehumidifier TTK 71 E

Cleaning the air filter

Note

Ensure that the air filter is not worn or damaged. The
corners and edges of the air filter must not be
deformed or rounded. Before reinserting the air filter,
make sure that it is undamaged and dry!

The air filter has to be cleaned as soon as it is dirty. This is
brought to light e.g. by a reduced capacity (see chapter Errors
and faults).

1. Remove the air filter from the device.

2. Clean the filter using a slightly damp, soft, lint-free cloth. If

the filter is heavily contaminated, clean it with warm water
mixed with a neutral cleaning agent.

3. Allow the filter to dry completely. Do not insert a wet filter

into the device!

4. Reinsert the air filter into the device.

Summary of Contents for ttk 71 e

Page 1: ...TRT BA TTK71E TC2013 05 007 EN TTK 71 E EN OPERATING MANUAL DEHUMIDIFIER...

Page 2: ...using the device Always store the manual in the immediate vicinity of the device or its site of use Warning Read all safety warnings and all instructions Failure to follow the warnings and instructio...

Page 3: ...ion the device in rooms where potentially leaking refrigerant cannot accumulate Only position the device in rooms where there is no source of ignition e g open flames an active gas appliance or an ele...

Page 4: ...ders all claims for liability and guarantee null and void Personnel qualifications People who use this device must be aware of the dangers that occur when working with electric devices in damp areas h...

Page 5: ...Information about the device Description of the device The device uses the principle of condensation to automatically dehumidify rooms The fan sucks damp room air through the air inlet the air filter...

Page 6: ...After transporting the device observe the following Set up the device in an upright position after transport Leave the device to rest for 12 to 24 hours so the refrigerant can accumulate within the co...

Page 7: ...ervice Only position the device in rooms where potentially leaking refrigerant cannot accumulate Only position the device in rooms where there is no source of ignition e g open flames an active gas ap...

Page 8: ...mage to the device Make sure that the air filter is installed before switching the device on Opening the ventilation flaps 1 Prior to switching the device on open the ventilation flaps at the air outl...

Page 9: ...s displayed when the timer is activated Indicates the number or hours set Is displayed automatic switch off enabled 17 TIMER button Starts programming for the timer function 18 MODE button Selection o...

Page 10: ...be adjusted in increments of 1 h Note Do not leave the operating device unattended in a freely accessible room with an activated timer Automatic switch off The device is switched on 1 Press the TIMER...

Page 11: ...The device does not start Check the power connection Check the power cable and mains plug for damage Check the on site fusing Check the filling level of the condensation tank and empty it if necessar...

Page 12: ...ed Disconnect the device from the mains and let it cool down for approx 10 minutes before reconnecting it The device might carry out an automatic defrost During automatic defrost the device does not d...

Page 13: ...or drain hose X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Check air inlets and outlets for dirt and foreign objects and cl...

Page 14: ...entire refrigerant circuit is a maintenance free hermetically sealed system and may only be maintained or repaired by specialist companies for cooling and air conditioning or by Trotec Safety signs a...

Page 15: ...air filter has to be cleaned as soon as it is dirty This is brought to light e g by a reduced capacity see chapter Errors and faults 1 Remove the air filter from the device 2 Clean the filter using a...

Page 16: ...ing or removing the condensation tank In doing so make sure that the float is positioned correctly Also make sure that the condensation tank is inserted correctly otherwise the device cannot be switch...

Page 17: ...ction side 1 2 MPa Pressure outlet side 2 5 MPa Max permissible pressure 2 5 MPa Mains supply 220 240 V 50 Hz Max power input 0 42 W Nominal current 1 8 A Refrigerant R290 Amount of refrigerant 55 g G...

Page 18: ...18 EN dehumidifier TTK 71 E Circuit diagram...

Page 19: ...Floater 1 20 Suction Tube 1 4 Back Cover Defence Net 1 21 Discharge Tube 1 5 Outlet Grids 1 22 Evaporator Inlet Tube 4 6 Back Cover 1 23 Condensor 1 7 Cover Right 1 24 Evaporator 1 8 Out Evaporator 1...

Page 20: ...dministration For further return options provided by us please refer to our website https de trotec com shop The separate collection of waste electrical and electronic equipment aims to enable the re...

Page 21: ...Trotec GmbH Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Reviews: