background image

EN

3

dehumidifier TTK 71 E

Ensure that all electric cables outside of the device are
protected from damage (e.g. caused by animals). Never
use the device if electric cables or the power connection
are damaged!

The electrical connection must correspond to the
specifications in chapter Technical data.

Insert the mains plug into a properly secured mains
socket.

Observe the device's power input, cable length and
intended use when selecting extensions to the power
cable. Completely unroll extension cables. Avoid electrical
overload.

Before carrying out maintenance, care or repair work on
the device, remove the mains plug from the mains socket.
Hold onto the mains plug while doing so.

Switch the device off and disconnect the power cable from
the mains socket when the device is not in use.

Do not under any circumstances use the device if you
detect damages on the mains plug or power cable. 
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
Defective power cables pose a serious health risk!

When positioning the device, observe the minimum
distances from walls and other objects as well as the
storage and operating conditions specified in the Technical
data chapter.

Make sure that the air inlet and outlet are not obstructed.

Make sure that the suction side is kept free of dirt and
loose objects.

Do not remove any safety signs, stickers or labels from the
device. Keep all safety signs, stickers and labels in legible
condition.

Only transport the device in an upright position with an
emptied condensation tank or drain hose.

Discharge the collected condensate before transport and
storage. Do not drink it. Health hazard!

Safety warnings for devices containing flammable
refrigerants

Only position the device in rooms where potentially leaking
refrigerant cannot accumulate.

Only position the device in rooms where there is no source
of ignition (e.g. open flames, an active gas appliance or an
electric heater).

Please note that the refrigerant is odourless.

Only install the device in compliance with the national
installation regulations.

Observe the national gas regulations.

Only install, operate and store the device 

TTK 71 E

 in a

room measuring more than 4 m

2

.

Store the device in a way that no mechanical damage can
occur.

Please note that the connected pipelines must not contain
any sources of ignition.

R290 is a refrigerant that complies with European
environmental regulations. No part of the cooling circuit
may be perforated.

Observe the maximum refrigerant capacity in the technical
data.

Do not drill through or burn.

Do not use any means other than those recommended by
the manufacturer for accelerating the defrosting process.

Every person working with or at the refrigerant circuit must
be able to provide a certificate of qualification issued by a
body accredited by the industry, demonstrating their
competence in the safe use of refrigerants based on a
procedure well-known in the industry.

Service work may only be carried out in accordance with
the manufacturer's specifications. If maintenance and
repair work require the support of additional persons, the
person trained in handling flammable refrigerants shall
continuously supervise the work carried out.

Unventilated rooms, in which the device is installed,
operated or stored, must be built in a way to ensure that
potentially leaking refrigerant cannot accumulate. This
serves to avoid fire or explosion hazards resulting from an
ignition of the refrigerant by an electric furnace, cooking
stove or another ignition source.

The entire refrigerant circuit is a maintenance-free,
hermetically sealed system and may only be maintained or
repaired by specialist companies for cooling and air-
conditioning or by Trotec.

Summary of Contents for ttk 71 e

Page 1: ...TRT BA TTK71E TC2013 05 007 EN TTK 71 E EN OPERATING MANUAL DEHUMIDIFIER...

Page 2: ...using the device Always store the manual in the immediate vicinity of the device or its site of use Warning Read all safety warnings and all instructions Failure to follow the warnings and instructio...

Page 3: ...ion the device in rooms where potentially leaking refrigerant cannot accumulate Only position the device in rooms where there is no source of ignition e g open flames an active gas appliance or an ele...

Page 4: ...ders all claims for liability and guarantee null and void Personnel qualifications People who use this device must be aware of the dangers that occur when working with electric devices in damp areas h...

Page 5: ...Information about the device Description of the device The device uses the principle of condensation to automatically dehumidify rooms The fan sucks damp room air through the air inlet the air filter...

Page 6: ...After transporting the device observe the following Set up the device in an upright position after transport Leave the device to rest for 12 to 24 hours so the refrigerant can accumulate within the co...

Page 7: ...ervice Only position the device in rooms where potentially leaking refrigerant cannot accumulate Only position the device in rooms where there is no source of ignition e g open flames an active gas ap...

Page 8: ...mage to the device Make sure that the air filter is installed before switching the device on Opening the ventilation flaps 1 Prior to switching the device on open the ventilation flaps at the air outl...

Page 9: ...s displayed when the timer is activated Indicates the number or hours set Is displayed automatic switch off enabled 17 TIMER button Starts programming for the timer function 18 MODE button Selection o...

Page 10: ...be adjusted in increments of 1 h Note Do not leave the operating device unattended in a freely accessible room with an activated timer Automatic switch off The device is switched on 1 Press the TIMER...

Page 11: ...The device does not start Check the power connection Check the power cable and mains plug for damage Check the on site fusing Check the filling level of the condensation tank and empty it if necessar...

Page 12: ...ed Disconnect the device from the mains and let it cool down for approx 10 minutes before reconnecting it The device might carry out an automatic defrost During automatic defrost the device does not d...

Page 13: ...or drain hose X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Check air inlets and outlets for dirt and foreign objects and cl...

Page 14: ...entire refrigerant circuit is a maintenance free hermetically sealed system and may only be maintained or repaired by specialist companies for cooling and air conditioning or by Trotec Safety signs a...

Page 15: ...air filter has to be cleaned as soon as it is dirty This is brought to light e g by a reduced capacity see chapter Errors and faults 1 Remove the air filter from the device 2 Clean the filter using a...

Page 16: ...ing or removing the condensation tank In doing so make sure that the float is positioned correctly Also make sure that the condensation tank is inserted correctly otherwise the device cannot be switch...

Page 17: ...ction side 1 2 MPa Pressure outlet side 2 5 MPa Max permissible pressure 2 5 MPa Mains supply 220 240 V 50 Hz Max power input 0 42 W Nominal current 1 8 A Refrigerant R290 Amount of refrigerant 55 g G...

Page 18: ...18 EN dehumidifier TTK 71 E Circuit diagram...

Page 19: ...Floater 1 20 Suction Tube 1 4 Back Cover Defence Net 1 21 Discharge Tube 1 5 Outlet Grids 1 22 Evaporator Inlet Tube 4 6 Back Cover 1 23 Condensor 1 7 Cover Right 1 24 Evaporator 1 8 Out Evaporator 1...

Page 20: ...dministration For further return options provided by us please refer to our website https de trotec com shop The separate collection of waste electrical and electronic equipment aims to enable the re...

Page 21: ...Trotec GmbH Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Reviews: