background image

10

EN

dehumidifier TTK 71 E

Setting the fan speed

You can choose between low and high fan speed (laundry drying
function).

1. Press the 

MODE

 button (18) to select either low or high fan

speed (laundry drying function).

ð

The selected fan speed is indicated by the 

HIGH

indication (20) for high fan speed, or by the 

LOW

indication (21) for low fan speed.

Automatic dehumidification

In this operating mode, the device operates fully automatically
depending on the room humidity level. The room humidity level
is preset to 55 % and cannot be changed.
The fan runs at high speed at humidity levels above 70 %. The
fan runs at low speed at humidity levels below 70 %.
If the humidity value falls below the preselected level, the
compressor will switch off automatically. The fan keeps
running. Once the preselected humidity level is exceeded, the
compressor switches back on.
Please proceed as follows to activate 

Automatic

dehumidification:

1. Press the 

MODE

 button (18) until the 

Auto

 indication (19)

appears.

ð

Automatic dehumidification

 is now activated.

Continuous operation

The device dehumidifies the air constantly and regardless of the
room humidity.
The relative humidity cannot be adjusted in this operating mode.

1. To start continuous operation mode, press the 

decrease

value

 (9) or 

increase value

 button (11) until 

CO

 is shown on

the segment display (10).

Info

For continuous operation a condensation drain hose
can be connected in order to continuously drain the
accumulating condensate.

Setting the timer

The timer has the following mode of operation:

automatic switch-off upon expiry of a preset number of
hours.

The number of hours can be between 0 and 12 and can be
adjusted in increments of 1 h.

Note

Do not leave the operating device unattended in a
freely accessible room with an activated timer.

Automatic switch-off

ü

The device is switched on.

1. Press the 

TIMER

 button (17).

ð

The 

TIMER

 indication (16) is enabled.

2. Press the 

increase value

 (11) or 

decrease value

 arrow

button (9) to set the desired number of hours.

3. Wait for approx. 5 seconds in order to save the setting.

ð

The segment display (10) shows the set number of hours
until switch-off.

ð

The timer setting equals the desired number of hours.

ð

The device switches off after the set period of time.

Auto stop function

If the water tank is full, not inserted correctly or the set room
humidity has been reached, the device will stop automatically.

Operation with hose attached to the condensation
connection

For continuous operation or unattended dehumidification, please
connect a suitable condensation drain hose to the device.

ü

A suitable hose (diameter: 12 mm) is ready for use.

ü

The device is switched off.

1. Push one end of the hose onto the hose connection.
2. Guide the other hose end to a suitable drain or sufficiently

dimensioned collection container. Please note that the
hose must not be kinked.

Remove the hose if you want to collect the condensate in the
condensation tank again. Allow the hose to dry prior to storage.
The hose can be connected in any operating mode for
continuous operation.

Automatic defrost

At low ambient temperatures, ice may form at the evaporator
during dehumidification. The device will then carry out an
automatic defrost. Dehumidification is briefly interrupted during
defrosting. The fan keeps running.

The duration of the defrost process can vary. Do 

not

 switch off

the device during automatic defrost. Do 

not

 remove the mains

plug from the mains socket.
The 

DEFROST

 indication (15) is illuminated during automatic

defrosting.

Summary of Contents for ttk 71 e

Page 1: ...TRT BA TTK71E TC2013 05 007 EN TTK 71 E EN OPERATING MANUAL DEHUMIDIFIER...

Page 2: ...using the device Always store the manual in the immediate vicinity of the device or its site of use Warning Read all safety warnings and all instructions Failure to follow the warnings and instructio...

Page 3: ...ion the device in rooms where potentially leaking refrigerant cannot accumulate Only position the device in rooms where there is no source of ignition e g open flames an active gas appliance or an ele...

Page 4: ...ders all claims for liability and guarantee null and void Personnel qualifications People who use this device must be aware of the dangers that occur when working with electric devices in damp areas h...

Page 5: ...Information about the device Description of the device The device uses the principle of condensation to automatically dehumidify rooms The fan sucks damp room air through the air inlet the air filter...

Page 6: ...After transporting the device observe the following Set up the device in an upright position after transport Leave the device to rest for 12 to 24 hours so the refrigerant can accumulate within the co...

Page 7: ...ervice Only position the device in rooms where potentially leaking refrigerant cannot accumulate Only position the device in rooms where there is no source of ignition e g open flames an active gas ap...

Page 8: ...mage to the device Make sure that the air filter is installed before switching the device on Opening the ventilation flaps 1 Prior to switching the device on open the ventilation flaps at the air outl...

Page 9: ...s displayed when the timer is activated Indicates the number or hours set Is displayed automatic switch off enabled 17 TIMER button Starts programming for the timer function 18 MODE button Selection o...

Page 10: ...be adjusted in increments of 1 h Note Do not leave the operating device unattended in a freely accessible room with an activated timer Automatic switch off The device is switched on 1 Press the TIMER...

Page 11: ...The device does not start Check the power connection Check the power cable and mains plug for damage Check the on site fusing Check the filling level of the condensation tank and empty it if necessar...

Page 12: ...ed Disconnect the device from the mains and let it cool down for approx 10 minutes before reconnecting it The device might carry out an automatic defrost During automatic defrost the device does not d...

Page 13: ...or drain hose X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Check air inlets and outlets for dirt and foreign objects and cl...

Page 14: ...entire refrigerant circuit is a maintenance free hermetically sealed system and may only be maintained or repaired by specialist companies for cooling and air conditioning or by Trotec Safety signs a...

Page 15: ...air filter has to be cleaned as soon as it is dirty This is brought to light e g by a reduced capacity see chapter Errors and faults 1 Remove the air filter from the device 2 Clean the filter using a...

Page 16: ...ing or removing the condensation tank In doing so make sure that the float is positioned correctly Also make sure that the condensation tank is inserted correctly otherwise the device cannot be switch...

Page 17: ...ction side 1 2 MPa Pressure outlet side 2 5 MPa Max permissible pressure 2 5 MPa Mains supply 220 240 V 50 Hz Max power input 0 42 W Nominal current 1 8 A Refrigerant R290 Amount of refrigerant 55 g G...

Page 18: ...18 EN dehumidifier TTK 71 E Circuit diagram...

Page 19: ...Floater 1 20 Suction Tube 1 4 Back Cover Defence Net 1 21 Discharge Tube 1 5 Outlet Grids 1 22 Evaporator Inlet Tube 4 6 Back Cover 1 23 Condensor 1 7 Cover Right 1 24 Evaporator 1 8 Out Evaporator 1...

Page 20: ...dministration For further return options provided by us please refer to our website https de trotec com shop The separate collection of waste electrical and electronic equipment aims to enable the re...

Page 21: ...Trotec GmbH Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com...

Reviews: