Adjusting the air pressure for the pump
Ideally, the air pressure should range between 0.32 bar and
0.36 bar. During operation, the air pressure can be read from
the pressure gauge (5).
Info
If the air pressure exceeds 0.36 bar, a flame emerges
from the air outlet of the device. The device then stops
running.
If the pressure is lower than 0.32 bar, the device
continues to operate, but with a reduced performance.
1. Adjust the air pressure during operation by means of a
slotted screwdriver. For lowering turn the screw counter-
clockwise; for increasing carefully turn it clockwise.
0,6
0,8
1
0
0,2
0,4
Technical annex
Technical data
Parameter
Value
Article number
1.430.000.066
Method of heating
direct
Amount of air
735 m³/h
Fan
Axial fan
Mains connection
1/N/PE~220–240 V / 50 Hz
Nominal heat output
30 kW (25,800 kcal)
Temperature increase ΔT
90 °C (1.5 m distance)
Input voltage
230 V / 50 Hz
Current consumption
0.8 A
Max. fuel consumption
2.9 l/h
Sound level (distance 1 m)
65 dB(A)
Weight
20 kg
Dimensions
(length x width x height)
388 x 942 x 460 (mm)
Minimum distance to walls or
other objects
3 m
Fuels
The following fuels are approved for the device:
•
EL fuel oil
•
Kerosene
•
Diesel