TX6356 User Manual
TX6356-UM-EN-01 7
1.5 Technical Information
Humidity sensing range
10 to 90% non-condensing
Accuracy
+/- 5%
Linearity
±2% FS
Operating temperature
range
-20 to +40°C
Storage temperature limits
-20 to + 60°C
Protection classification
Housing - dust and waterproof to IP65
Sensor head - protected to IP54
Housing material
Reinforced polymer
Sensor housing material
Polycarbonate
Nett weight
750 g
Information display
128 x 64 dot graphic backlit LCD screen
Mounting
Two 6.5 mm diameter fixing holes with Unistrut
6946 indents
Cable entries
1 x M20
Electrical connections
4 mm barrier/clamp terminals with circuit
segregation barriers
Conductors
A maximum of two per terminal
Conductor size
A maximum of 2 x 2.5 mm²
Terminal torque
•
2.4 Nm maximum
Vibration limits
Vibration limits (EN 60079-29-1):
•
10 to 30 Hz - 1.00 mm total excursion
•
31 to 150 Hz - 19.6 m/s
2
acceleration peak
Impact limits
20 joules (housing)
Output Signals
•
0.4 to 2 V
•
4 to 20 mA
•
5 to 15 Hz
•
Dual relay contacts (normally open OR
normally closed)
•
RS485 data
Alarms
Programmable
General
and
High
alarm levels
with LED indicators
www.trolex.com
Summary of Contents for TX6356
Page 1: ......
Page 2: ......
Page 6: ...6 TX6356 UM EN 01 1 4 Dimensions www trolex com ...
Page 16: ...16 TX6356 UM EN 01 4 Setup and Calibration 4 1 Controls and Indicators www trolex com ...
Page 17: ...TX6356 User Manual TX6356 UM EN 01 17 www trolex com ...
Page 18: ...18 TX6356 UM EN 01 4 2 Software Menus www trolex com ...
Page 55: ......
Page 56: ......