background image

C o m f o r t

B R E E Z E  

T M

  M o d e l   C B 3 0 0

I n s t a l l a t i o n ,   O p e r a t i o n ,   &   M a i n t e n a n c e   M a n u a l

8

w w w. t r i o n i a q . c o m

6. Maintenance & Troubleshooting

!

DANGER - RISK OF ELECTRIC SHOCK

Before cleaning, servicing, or parts replacement, the unit must 

be disconnected from all sources of electricity.

6.1 Pad Replacement

It will become necessary to replace the pad inside your 

ComfortBREEZE  CB300/CB300S  humidifier  as  time  goes  on.   

A red LED Service indicator light may light up.  This will tell 

you that it is time to service your humidifier.  Please refer the 

following procedure.

1.  Adjust Humidistat to the lowest setting to ensure that 

there is no call for humidity.

2. 

Ensure that power to the humidifier has been turned off 

so  that  the  humidifier  will  not  operate  while  service  is 

being performed.

3. 

Close the water supply valve so that no water may flow to 

the humidifier during servicing.

4. 

To remove the humidifier cover, press the release pads 

as shown in Figure 10 and pull the cover toward you.  

5. 

To remove the evaporator pad, push the retaining clips 

and pull the top pad retainer out from the base.  The 
retainer and pad will come out together.  The drain pan 
stays inside the unit.  See Figure 11.

6. 

Reassemble the humidifier.

7. 

If required, reset the service timer (RED LED) by pressing 

the reset button on the circuit board (if equipped) for 3 
seconds. CB300S units with H

2

OSmart™  Technology 

include a circuit board.

Figure 10

Heat Pump System: Humidifier operates 

upon call-for-humidity only during a call-for-
heat.
• 

DIP Switch #3: Off

• 

DIP Switch #4: Off

• 

Air Proving Switch: Required

• 

Go Terminal: No Connection

• 

W/G Terminal: No Connection

Heat Pump System: Humidifier operates 

upon a call-for-humidity and will start the 
HVAC blower.
• 

DIP Switch #3: Off

• 

DIP Switch #4: On

• 

Air Proving Switch: Recommended but not required.  

If no air proving switch is used, install a jumper across 

the AP1/AP2 terminals

• 

Go Terminal: Connected to System “G”

• 

W/G Terminal: No Connection

5. Operation

Once the CB300/CB300S is installed and ready to be started, 

the humidistat and DIP switches on the control board within 

the  humidifier  unit  must  be  configured.    The  CB300  without 

the  H

2

OSmart™  controls does not have any DIP switches to 

configure.  You may skip to the Preliminary Checkout and Start-

up Sequence.

5.1 Preliminary Checkout and Start-up Sequence

1.  Check that unit drain plumbing is properly connected and 

drained.

2.  Ensure that the supply plumbing is installed properly.
3.  Open cold water supply and insure water is reaching the 

unit.  Incoming water line should be filtered.

4. 

With the unit powered, when the humidistat has a “call for 

humidity”, the indicator LED will illuminate Green and the 

unit will begin operation. 

5.  If at any point the indicator LED illuminates red or blinks 

red/green alternating, a fault has been detected; service 

will be required and the fault must be reset. Refer to the 
Maintenance & Troubleshooting section.

6.  Refer to the humidistat manual for “call for humidity” 

percentage settings.

5.2 Starting/Stopping the unit

In order to start and stop the unit you must only lower the 
humidistat setting to a point at which the contacts are open. 

X

X

X

X

X

X

X

X

X

X

Summary of Contents for ComfortBREEZE CB300

Page 1: ...T R I O N w w w t r i o n i a q c o m ComfortBREEZE TM CB300 CB300S Flow Through Evaporative Humidifier READ AND SAVE THESE INSTRUCTIONS...

Page 2: ...ox 4 3 3 Unit Specifications 4 4 Installation 4 4 1 Clearances 5 4 2 Mounting 5 4 3 Plumbing 6 4 4 Electrical Wiring 6 4 4 1 Wiring CB300 without water saving controls 6 4 4 2 Wiring CB300S with H2OSm...

Page 3: ...rts or components and does not include the payment of the cost of labor charges to remove or replace such defective components or parts 7 TRION will not be responsible for loss of use of any product l...

Page 4: ...A lower setting may be necessary to prevent condensation on windows during the coldest part of the winter An electronic humidistat is supplied with CB300S units that can automatically adjust the setp...

Page 5: ...30 40 relative humidity If condensation occurs on windows the humidistat setting must be lowered to prevent condensation damage DO NOT install the humidifier where freezing temperatures may occur DO...

Page 6: ...rocess Once this is complete close the saddle valve 3 Attach the line to the humidifier by simply pushing the line into the push to lock fitting and pulling back slightly to seat the line If it become...

Page 7: ...Typical furnace bonnet temperature is nominally 120 F DIP 4 Furnace Runs Fan Humidifier Runs Fan In most systems the HVAC system operates the main blower The CB300S has a 24VAC output that may be used...

Page 8: ...humidity only during a call for heat DIP Switch 3 Off DIP Switch 4 Off Air Proving Switch Required Go Terminal No Connection W G Terminal No Connection Heat Pump System Humidifier operates upon a cal...

Page 9: ...unit will not operate until airflow is present 2 Slow Red Blink Once the solenoid valve is energized and humidification has begun the controls must see a change in temperature or the unit will not be...

Page 10: ...hat there is power supplied to the valve Check control board output Circuit Board has failed fuse is blown Replace circuit board LED is glowing solid RED Service Timer has expired Replace the humidifi...

Page 11: ...300 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 11 www trioniaq com 7 Exploded Views Parts List 7 1 CB300S Exploded View 1 2 3 4 5 6 7 8 9 10 11 12 13 14 16 17 18 19 20...

Page 12: ...rtBREEZE TM Model CB300 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 12 www trioniaq com 7 2 CB300 Exploded View 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Figur...

Page 13: ...ID VALVE ASSEMBLY 1 8 265508 002 CONTROL BOARD CB300S 2 2 11 265698 001 PNEUMATIC PUSH TO CONNECT FITTING 1 12 G 128 FLUID RESTRICTOR 1 12 G 217 FLUID RESTRICTOR 1 1 14 265470 001 PAD EVAPORATOR 1 15...

Page 14: ...Form No 265817 001 Rev 11 15 TRION 2015 All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com...

Reviews: