background image

C o m f o r t

B R E E Z E  

T M

  M o d e l   C B 3 0 0

I n s t a l l a t i o n ,   O p e r a t i o n ,   &   M a i n t e n a n c e   M a n u a l

5

w w w. t r i o n i a q . c o m

Figure 3: Upflow - Bottom Return

Figure 4: Downflow

4.1 Recommended Minimum Installation Clearance

Left

3 inches

Right

3 inches

Top

2 inches

Bottom

6 inches

Back

12 inches

Side  Clearance  (Left  or  Right)  must  be  sufficient  to 

accommodate the by-pass duct connection.  Evaluate 
installation location as needed to ensure there is space 
available.

!

CAUTION

TRION  recommends  that  this  humidifier  be  installed  by  a 

trained HVAC professional.  Do not connect the unit to the 
power source until the installation is complete.  A thorough 
checkout of the unit installation should be completed before 
operating the unit.  Failure to follow these directions may void 
the manufacturer’s original warranty.

4.2 Mounting

The ComfortBREEZE

  CB300/CB300S  humidifier  may  be 

mounted directly to the warm air supply duct or the return duct 
of your HVAC system.  Certain conditions must be met to ensure 
proper unit operation.  Refer to the following list.
• 

Ensure that the duct surface is reinforced, if necessary, to 

allow the unit to remain level and plumb.

• 

Ensure that the humidifier has adequate clearance to allow 

for the removal and replacement of the evaporator pad.

• 

When  installing  the  humidifier  in  an  attic  or  above  a 

ceiling, a drain tray must be installed under the unit as a 

precautionary measure to prevent water damage from 
occurring if a leak develops.

• 

The  recommended  humidistat  range  is  30-40%  relative 

humidity.  If condensation occurs on windows, the humidistat 

setting must be lowered to prevent condensation damage.

• 

DO NOT install the humidifier where freezing temperatures 

may occur.

• 

DO NOT install the humidifier where it interferes with the 

furnace access panels.

• 

DO NOT install the humidifier close to a flue pipe.  Intense 

heat may damage the humidifier.

• 

DO  NOT  mount  the  humidifier  in  the  jacket  of  a  cased 

coil.    It  is  preferable  to  mount  the  humidifier  immediately 

downstream of the cased coil, if present.  Ensure that the 

humidifier does not interfere with the coil ends.

• 

DO NOT mount the humidifier in a furnace jacket.

• 

DO NOT install on gravity hot air systems.

• 

DO NOT connect a hot water supply to ComfortBREEZE 

humidifiers  that  are  equipped  with  water  saving  controls. 

(H

2

OSmart™ Technology).

1. 

Tape the mounting template to the duct so that it is flat and 

the top edge is level.

2.  Carefully remove the center of the template by tearing 

along the perforated lines.  Use a marker to trace on the 
duct along the cutout opening.

!

WARNING

Electrical power to the furnace must be disconnected before 
proceeding. Serious injury or death may result.

3.  Drill the holes marked on the template.  Remove the 

template from the duct and carefully cut the duct along 
the outside edge of the rectangle that was traced by the 
marker.  Remove any burrs from the cut edge of the sheet 
metal taking care not to injure yourself.

4.  Apply the gasket material found in the accessory bag to the 

duct around the rectangular cutout.

5. 

Lift  the  humidifier  into  the  rectangular  opening  so  that 

the plastic tabs engage the lower edge of the rectangular 
opening.  The tabs should be on the inside of the duct.  Tilt 

Summary of Contents for ComfortBREEZE CB300

Page 1: ...T R I O N w w w t r i o n i a q c o m ComfortBREEZE TM CB300 CB300S Flow Through Evaporative Humidifier READ AND SAVE THESE INSTRUCTIONS...

Page 2: ...ox 4 3 3 Unit Specifications 4 4 Installation 4 4 1 Clearances 5 4 2 Mounting 5 4 3 Plumbing 6 4 4 Electrical Wiring 6 4 4 1 Wiring CB300 without water saving controls 6 4 4 2 Wiring CB300S with H2OSm...

Page 3: ...rts or components and does not include the payment of the cost of labor charges to remove or replace such defective components or parts 7 TRION will not be responsible for loss of use of any product l...

Page 4: ...A lower setting may be necessary to prevent condensation on windows during the coldest part of the winter An electronic humidistat is supplied with CB300S units that can automatically adjust the setp...

Page 5: ...30 40 relative humidity If condensation occurs on windows the humidistat setting must be lowered to prevent condensation damage DO NOT install the humidifier where freezing temperatures may occur DO...

Page 6: ...rocess Once this is complete close the saddle valve 3 Attach the line to the humidifier by simply pushing the line into the push to lock fitting and pulling back slightly to seat the line If it become...

Page 7: ...Typical furnace bonnet temperature is nominally 120 F DIP 4 Furnace Runs Fan Humidifier Runs Fan In most systems the HVAC system operates the main blower The CB300S has a 24VAC output that may be used...

Page 8: ...humidity only during a call for heat DIP Switch 3 Off DIP Switch 4 Off Air Proving Switch Required Go Terminal No Connection W G Terminal No Connection Heat Pump System Humidifier operates upon a cal...

Page 9: ...unit will not operate until airflow is present 2 Slow Red Blink Once the solenoid valve is energized and humidification has begun the controls must see a change in temperature or the unit will not be...

Page 10: ...hat there is power supplied to the valve Check control board output Circuit Board has failed fuse is blown Replace circuit board LED is glowing solid RED Service Timer has expired Replace the humidifi...

Page 11: ...300 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 11 www trioniaq com 7 Exploded Views Parts List 7 1 CB300S Exploded View 1 2 3 4 5 6 7 8 9 10 11 12 13 14 16 17 18 19 20...

Page 12: ...rtBREEZE TM Model CB300 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 12 www trioniaq com 7 2 CB300 Exploded View 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Figur...

Page 13: ...ID VALVE ASSEMBLY 1 8 265508 002 CONTROL BOARD CB300S 2 2 11 265698 001 PNEUMATIC PUSH TO CONNECT FITTING 1 12 G 128 FLUID RESTRICTOR 1 12 G 217 FLUID RESTRICTOR 1 1 14 265470 001 PAD EVAPORATOR 1 15...

Page 14: ...Form No 265817 001 Rev 11 15 TRION 2015 All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com...

Reviews: