C o m f o r t
B R E E Z E
T M
M o d e l C B 3 0 0
I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l
5
w w w. t r i o n i a q . c o m
Figure 3: Upflow - Bottom Return
Figure 4: Downflow
4.1 Recommended Minimum Installation Clearance
Left
3 inches
Right
3 inches
Top
2 inches
Bottom
6 inches
Back
12 inches
Side Clearance (Left or Right) must be sufficient to
accommodate the by-pass duct connection. Evaluate
installation location as needed to ensure there is space
available.
!
CAUTION
TRION recommends that this humidifier be installed by a
trained HVAC professional. Do not connect the unit to the
power source until the installation is complete. A thorough
checkout of the unit installation should be completed before
operating the unit. Failure to follow these directions may void
the manufacturer’s original warranty.
4.2 Mounting
The ComfortBREEZE
CB300/CB300S humidifier may be
mounted directly to the warm air supply duct or the return duct
of your HVAC system. Certain conditions must be met to ensure
proper unit operation. Refer to the following list.
•
Ensure that the duct surface is reinforced, if necessary, to
allow the unit to remain level and plumb.
•
Ensure that the humidifier has adequate clearance to allow
for the removal and replacement of the evaporator pad.
•
When installing the humidifier in an attic or above a
ceiling, a drain tray must be installed under the unit as a
precautionary measure to prevent water damage from
occurring if a leak develops.
•
The recommended humidistat range is 30-40% relative
humidity. If condensation occurs on windows, the humidistat
setting must be lowered to prevent condensation damage.
•
DO NOT install the humidifier where freezing temperatures
may occur.
•
DO NOT install the humidifier where it interferes with the
furnace access panels.
•
DO NOT install the humidifier close to a flue pipe. Intense
heat may damage the humidifier.
•
DO NOT mount the humidifier in the jacket of a cased
coil. It is preferable to mount the humidifier immediately
downstream of the cased coil, if present. Ensure that the
humidifier does not interfere with the coil ends.
•
DO NOT mount the humidifier in a furnace jacket.
•
DO NOT install on gravity hot air systems.
•
DO NOT connect a hot water supply to ComfortBREEZE
humidifiers that are equipped with water saving controls.
(H
2
OSmart™ Technology).
1.
Tape the mounting template to the duct so that it is flat and
the top edge is level.
2. Carefully remove the center of the template by tearing
along the perforated lines. Use a marker to trace on the
duct along the cutout opening.
!
WARNING
Electrical power to the furnace must be disconnected before
proceeding. Serious injury or death may result.
3. Drill the holes marked on the template. Remove the
template from the duct and carefully cut the duct along
the outside edge of the rectangle that was traced by the
marker. Remove any burrs from the cut edge of the sheet
metal taking care not to injure yourself.
4. Apply the gasket material found in the accessory bag to the
duct around the rectangular cutout.
5.
Lift the humidifier into the rectangular opening so that
the plastic tabs engage the lower edge of the rectangular
opening. The tabs should be on the inside of the duct. Tilt