background image

C o m f o r t

B R E E Z E  

T M

  M o d e l   C B 3 0 0

I n s t a l l a t i o n ,   O p e r a t i o n ,   &   M a i n t e n a n c e   M a n u a l

7

w w w. t r i o n i a q . c o m

4.4.2 Wiring Model CB300S (H

2

OSmart™ equipped model)

The CB300S is equipped with a circuit board that controls when 
the water valve is powered.  Figure 8 shows the main parts of 
the board.  Refer to Figure 9 for the wiring diagram.  Refer to 
the wiring notes shown after Figure 9 for board wiring/control 

configurations that explain how to set the board based upon the 

type of system it is being installed on.  These recommendations 
will provide the best performance and water savings depending 
on the type of furnace system.

LOW VOLTAGE

TERMINALS

DIP SWITCHES

RESET

BUTTON

THERMISTOR

CONNECTORS

LED

VALVE

CONNECTOR

The source of 24 VAC comes from the HVAC system terminals.  

The typical terminal designators are used, such as R, C, G, W, 

etc.  The following list identifies the low voltage terminals and 

their respective connection.

• 

R = 24 VAC from the HVAC system

• 

C= 24 VAC common from the HVAC system

• 

Hr = 24 VAC output for powering the electronic humidistat 
(if equipped)

• 

Hc = 24 VAC common for the electronic humidistat (if 
equipped)

• 

H = Humidistat input (must be 24 VAC)

• 

W/G = Input from HVAC system.  This is used when the 

humidifier is used with warm air furnaces.  

• 

AP1/AP2 = Air proving switch is connected here.  Do not 
apply voltage.

• 

Go = 24 VAC output may be used to energize a relay or 
connected back to the thermostat “G” terminal to turn on 
the fan.  Thermostat functionality may vary and affect the 
operation of this output.

DIP Switches/Settings:

• 

DIP  #1  =  Bypass  OFF  or  Motorized  ON  (Factory  Set 

Mode)

• 

DIP  #2  =  High  Capacity/Low  Capacity  - This  is  factory 

set to High Capacity.  If you determine that the humidifier 

is too large for the load, you may change the DIP switch 

position to ON.  It is not necessary in most cases.

• 

DIP  #3  =  Temperature  Check  -  If  you  are  installing  this 

humidifier  on  a  system  that  will  have  duct  temperatures 

regularly below 100°F, set this DIP switch to the OFF position.  

Typical furnace bonnet temperature is nominally 120°F.

• 

DIP  #4  =  Furnace  Runs  Fan/Humidifier  Runs  Fan  -  In 

most systems the HVAC system operates the main 
blower.  The CB300S has a 24VAC output that may be 
used to start the main blower if you would like to be able 

to get some humidification while the furnace is off.

• 

DIP  #5  =  Temperature  Override  -  This  DIP  switch 

is factory set to OFF.  In the event of a T1 thermistor 

failure, this switch may be set to ON.  This will allow the 

humidifier to operate temporarily with a single thermistor 

until a replacement is acquired. 

Wiring Notes (CB300S only):

When installing the CB300S on a furnace system, the humidifier 

may operate only when there is a call-for-heat OR the humidifier 

may be configured to start the HVAC blower whenever there is 

a call-for-humidity.

Single  Stage  Furnace:  Humidifier  operates 

upon call-for-humidity only during a call-for-
heat.
• 

DIP Switch #3: On

• 

DIP Switch #4: Off

• 

Air Proving Switch: Recommended but not required.  If 

no air proving switch is used, install a jumper across 

the AP1/AP2 terminals

• 

Go Terminal: No Connection

• 

W/G Terminal: Connected to System “W”

Multi  Stage/Modulating  Furnace:  Humidifier 

operates upon call-for-humidity only during a 
call-for-heat.
• 

DIP Switch #3: Off

• 

DIP Switch #4: Off

• 

Air Proving Switch: Required

• 

Go Terminal: No Connection

• 

W/G Terminal: No Connection

Single  or  Multi  Stage  Furnace:  Humidifier 

operates upon a call-for-humidity and will 
start the HVAC blower.
• 

DIP Switch #3: Off

• 

DIP Switch #4: On

• 

Air Proving Switch: Recommended but not required.  If 

no air proving switch is used, install a jumper across  

the AP1/AP2 terminals

• 

Go Terminal: Connected to System “G”

• 

W/G Terminal: No Connection

Although the capacity of the humidifier may be reduced by more 

than 40%, the CB300S may be installed on a heat pump system 

and  configured  to  operate  only  when  there  is  a  call-for-heat 

OR the humidifier may be configured to start the HVAC blower 

whenever there is a call-for-humidity.

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

Figure 8

SOLENOID

VALVE

YEL

YEL

DUCT THERMISTOR

UNIT THERMISTOR

MANUAL

HUMIDISTAT

SWITCH

AIR PROVING

HUMIDISTAT

ELECTRONIC

OR

TERMINALS. SEE

FROM SYSTEM

WIRING NOTES

TERMINALS. SEE

TO SYSTEM

WIRING NOTES

Figure 9

Summary of Contents for ComfortBREEZE CB300

Page 1: ...T R I O N w w w t r i o n i a q c o m ComfortBREEZE TM CB300 CB300S Flow Through Evaporative Humidifier READ AND SAVE THESE INSTRUCTIONS...

Page 2: ...ox 4 3 3 Unit Specifications 4 4 Installation 4 4 1 Clearances 5 4 2 Mounting 5 4 3 Plumbing 6 4 4 Electrical Wiring 6 4 4 1 Wiring CB300 without water saving controls 6 4 4 2 Wiring CB300S with H2OSm...

Page 3: ...rts or components and does not include the payment of the cost of labor charges to remove or replace such defective components or parts 7 TRION will not be responsible for loss of use of any product l...

Page 4: ...A lower setting may be necessary to prevent condensation on windows during the coldest part of the winter An electronic humidistat is supplied with CB300S units that can automatically adjust the setp...

Page 5: ...30 40 relative humidity If condensation occurs on windows the humidistat setting must be lowered to prevent condensation damage DO NOT install the humidifier where freezing temperatures may occur DO...

Page 6: ...rocess Once this is complete close the saddle valve 3 Attach the line to the humidifier by simply pushing the line into the push to lock fitting and pulling back slightly to seat the line If it become...

Page 7: ...Typical furnace bonnet temperature is nominally 120 F DIP 4 Furnace Runs Fan Humidifier Runs Fan In most systems the HVAC system operates the main blower The CB300S has a 24VAC output that may be used...

Page 8: ...humidity only during a call for heat DIP Switch 3 Off DIP Switch 4 Off Air Proving Switch Required Go Terminal No Connection W G Terminal No Connection Heat Pump System Humidifier operates upon a cal...

Page 9: ...unit will not operate until airflow is present 2 Slow Red Blink Once the solenoid valve is energized and humidification has begun the controls must see a change in temperature or the unit will not be...

Page 10: ...hat there is power supplied to the valve Check control board output Circuit Board has failed fuse is blown Replace circuit board LED is glowing solid RED Service Timer has expired Replace the humidifi...

Page 11: ...300 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 11 www trioniaq com 7 Exploded Views Parts List 7 1 CB300S Exploded View 1 2 3 4 5 6 7 8 9 10 11 12 13 14 16 17 18 19 20...

Page 12: ...rtBREEZE TM Model CB300 I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 12 www trioniaq com 7 2 CB300 Exploded View 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Figur...

Page 13: ...ID VALVE ASSEMBLY 1 8 265508 002 CONTROL BOARD CB300S 2 2 11 265698 001 PNEUMATIC PUSH TO CONNECT FITTING 1 12 G 128 FLUID RESTRICTOR 1 12 G 217 FLUID RESTRICTOR 1 1 14 265470 001 PAD EVAPORATOR 1 15...

Page 14: ...Form No 265817 001 Rev 11 15 TRION 2015 All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com...

Reviews: