Ensure that:
1. The shield pin is grounded as close to
the MC206X as possible.
2. 0V, V- and E- connections are NOT used
for terminating screens.
3. Pin 5 of Encoder/Stepper plug is
connected to 0V on drive.
4. Encoder cable screen is clamped to 9
way D shell.
5. MC206X 24V supply has common 0V with
the
drive(s)
When wiring MC206X Stepper outputs to
a differential input stepper drive, use the
0V and shield connections shown for the
encoder. The stepper drive must have its
common 0V connected to the MC206X 24V
return. (24V -)
Follow the wiring instructions for the daughter board that is
installed. In addition, because the daughter board front panel is
f tted within the MC206X plastic case, a separate shield ground wire
should be connected to all screened cables. This includes all cables
terminated with a D-type multi-pin connector.
GROUNDING AND
SHIELDING
USE OF
DAUGHTER
BOARD
* Encoder input 0V MUST be connected to pin 5