background image

the clamping plates. For best system performance, the power (+ and -) wires 
and the communication circuit wires should be twisted pair or shielded cable 
installed in a separate grounded conduit to protect the communication loop 
from electrical interference.

Make wire connections by stripping about 

3

/

8

" (10 mm) of insulation from the 

end of the wire. Then, slide the bare end of the wire under the appropriate 
clamping plate (See Figure 1), and tighten the clamping plate screw. Do NOT 
loop the wire under the clamping plate. (See Figure 2.) The wiring diagram for 
a typical 2-wire intelligent system is shown in Figure 4.

CAUTION

For system monitoring - for terminals 2, 3, 4, and 5, do not use looped wire 
under terminals. Break wire run as shown in Figure 2 to provide monitoring 
of connections.

FIGURE 1.  

FIGURE 2. 

1

1

22

33

44

55

66

 

C0471-07  

C0473-00

TR-B200S-WH/TR-B200S-IV TERMINALS 

No. Function

1.  Not Used

2.  Positive (+) Comm. Line In and Out

3.  Negative (-) Comm. Line In and Out

4.  External Supply Positive (+)

5.  External Supply Negative (-)

6.  Remote Annunciator 

FIGURE 3. MOUNTING

 

 C0891-07

MOUNTING

Mount the TR-B200S-WH/TR-B200S-IV mounting plate directly to an electri-
cal box. The plate will mount directly to 4" (10.2cm) square (with and with-
out plaster ring), 4" (10.2cm) octagon, 3

1

/

2

" (8.9 cm) octagon, single gang or 

double gang junction boxes.

1. Connect field wiring to terminals, as shown in Figure 1 and 2.

2. Attach the mounting plate to the junction box as shown in Figure 3.

3.  To mount the sounder base, hook the tab on the sounder base to the groove 

on the mounting plate.

4.  Then, swing the sounder base into position to engage the pins on the  

product with the terminals on the mounting plate.

5. Secure the sounder base by tightening the mounting screws.

6.  Install a compatible smoke sensor as described in the installation manual 

for the sensor.

CAUTION

Do not over tighten mounting plate screws; this may cause mounting plate 
to flex.

TAMPER RESISTANT FEATURE

NOTE: Do not use the tamper-resist feature if the removal tool is to be used. 
This detector base includes a tamper-resist feature that prevents its removal 
from the base without the use of a tool. To activate this feature, break the tab 
from the detector base as shown in Figure 7A. Then, install the detector. To 
remove the detector from the base once the tamper-resist feature has been 
activated, insert a small-bladed screwdriver into the slot from the top and 
press down on the lever (see Figure 7B). This allows the detector to be rotated 
counterclockwise for removal. The tamper-resist feature can be defeated by 
breaking and removing the plastic lever from the base. However, this prevents 
the feature from being used again.

TESTING AND MAINTENANCE

Sensors and bases must be tested after installation and as an integral part 
of a periodic maintenance program. Test the TR-B200S-WH/TR-B200S-IV as 
follows: 

NOTE: Before testing, notify the proper authorities that the smoke sensor 
system is undergoing maintenance and, therefore, will be temporarily out of 
service. Disable the system undergoing maintenance to prevent unwanted 
alarms.
1. 

 

Via the fire alarm control panel, command the individual 
TR-B200S-WH/TR-B200S-IV to activate using the associated sensor address. 
That sounder base should sound in approximately five seconds.

2.  Via the fire alarm control panel, command all TR-B200S-WH/TR-B200S-IV 

sounder bases to activate using group communication to all associated ad-
dresses. All devices on the loop should sound, and if a temporal tone is 
commanded, the tones can be synchronized to each other.

NOTE: Synchronization requires a power supply capable of producing the Sys-
tem Sensor synchronization pulses or a synchronization module.

When performing maintenance on connected smoke sensors, carefully note 
the location and address of each removed sensor. When re-installed, the 
TR-B200S-WH/TR-B200S-IV will confirm that address of the sensor matches 
the address stored in the sounder base memory. If there is a mismatch, this 
will be communicated to the fire alarm control panel and the sounder base 
can be commanded to chirp at regular intervals until the correct head is in-
stalled.

If a replacement head is installed or address changes are required, the mismatch 
may be resolved at the panel by commanding the TR-B200S-WH/TR-B200S-IV 
sounder base to re-enter its address learning mode and adopting the address 
of the new sensor.

  

I56-3387TRG-009 

 

 4/22/2021

Summary of Contents for TR-B200S-WH

Page 1: ...gh volume setting 15 mA maximum at low volume setting SLC Electrical Ratings SLC Operating Voltage 15 to 32 VDC SLC Standby Current 300 μA maximum Sound Output High Volume Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet 3 1m 24 Volts in continuous tone Low Volume Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet 3 1m 24 Volts in continuous tone The s...

Page 2: ... the base without the use of a tool To activate this feature break the tab from the detector base as shown in Figure 7A Then install the detector To remove the detector from the base once the tamper resist feature has been activated insert a small bladed screwdriver into the slot from the top and press down on the lever see Figure 7B This allows the detector to be rotated counterclockwise for remo...

Page 3: ...C NAC OPTIONAL REMOTE ANNUNCIATOR MODEL RA400Z 100Z E O L A SEPARATE SYNCHRONIZATION MODULE MAY BE USED TO PROVIDE THE SYNCHRONIZATION PULSES HORN HORN STROBE UL LISTED COMPATIBLE CONTROL PANEL UL LISTED 24V POWER SUPPLY WHEN USING 24V CONSTANT POWER AUX POWER ADDITIONAL POWER SUPERVISION RELAYS AND MODULES WILL BE REQUIRED FOR PROVIDING SUPERVISION WHEN THE SOUNDER BASES ARE INACTIVE CLASS A OPTI...

Page 4: ...l wiring configurations see your sync module manual FACP 1 EOL 1 HORN CONTROL ZONE 1 IN ZONE 2 IN SLAVE IN ZONE 1 OUT ZONE 2 OUT NAC SLAVE IN SLAVE OUT TEMP JUMP OFF NAC 1 B B NAC 2 B B NAC 3 B B TO NEXT DEVICE OR EOL 1 TO NEXT DEVICE OR EOL 1 2 STYLE Y ZONES CLASS B MASTER SOUNDER BASE SOUNDER BASE OPTIONAL FIGURE 7B REMOVING THE DETECTOR HEAD FROM THE BASE SLOT SLOT C1082 00 Triga is a trademark...

Reviews: