background image

 

©

 

2012 Tridonic

 

 Page 5 of 8 

2.2 Programming the entire parameter list 

All parameters must be newly set or checked at the time of initial programming. 
To do this, proceed as follows: 
 

 

Function Button 

Display 

Switch on the programming device 

 

SMART 
Programmer 
Version 2.30 

Go to the “Download/Program” menu item 

 

<downld/progr> 

Select the <downld/progr> menu 

 

download all 

Load all the stored parameters from the DSI-SMART (PTM)/basicDIM 
ILD in the DSI-SMART Programmer. (The light is switched off 
throughout this entire process. The DSI-SMART (PTM)/basicDIM ILD 
switches back to automatic mode after data transfer has successfully 
completed.) 

 

download all 
reading....OK 

All the parameters are now stored in the programming device. Quit 
this menu item 

 

<downld/progr> 

Go to the “Basic Parameters” menu item 

 

<basic param> 

Confirm. The adjustable parameter is then shown on the first line. 
The current value (e.g. 65) can also be seen on the first line. Possible 
settings are displayed on the second line. 

 

light level: 65 
1-100/max/man 

If this value is to be modified, select it by pressing the “Select” button. 
The asterisk in the top right hand corner indicates that the setting can 
be modified. 

 

light level: 65 * 
1-100/max/man 

Use the “Scroll” buttons to select the desired value. 

 

light level: 70 * 
1-100/max/man 

10  Quit this menu item. The previously set value is retained. 

 

light level: 70 
1-100/max/man 

11  Select the next parameter. 

 

t-delay: 10 min 
30s-60min/cont. 

12  Press “Select” to make this parameter modifiable. (Example: currently 

10min) 

 

t-delay:  10 min*
30s-60min/cont. 

13  Use the “Up/Down” buttons to set the new value (e.g. 20min). 

 

t-delay:  20 min*
30s-60min/cont. 

14  Quit this menu item. 

 

t-delay:  20 min 
30s-60min/cont. 

15  Repeat this procedure until all the parameters have been set as 

required. A list of all the parameters can be found in  
Section 2.1: Adjustable parameters 

 

 

16  When all parameters have been set, quit the <parameter> menu item 

 

<basic param> 

17  Go to <downld/progr> 

 

<downld/progr> 

18  Select the <downld/progr> menu 

 

download all 

19  Go to <programm all> 

 

program all 

20  Transfer all the stored parameters from the DSI-SMART Programmer 

to the DSI-SMART (PTM)/basicDIM ILD. (The light is switched off 
throughout this entire process. The DSI-SMART (PTM)/basicDIM ILD 
switches back to automatic mode after data transfer has successfully 
completed.) 

 

program all 
sending....OK 

 

All the parameters are now stored in the DSI-SMART 
(PTM)/basicDIM ILD.  

 

 

 

Summary of Contents for DSI-SMART

Page 1: ...eneral information 2 1 1 Overview of DSI SMART Programmer 2 2 Programming the main parameters 3 2 1 Adjustable parameters 3 2 2 Programming the entire parameter list 5 2 3 Programming individual parameters 6 3 Monitoring 7 4 Remote control 7 5 System tests 7 6 Status and error messages 8 7 Reset DSI SMART PTM basicDIM ILD to factory settings 8 ...

Page 2: ... the LCD display The lower line the status bar shows the possible settings for the menu item in question the current status and any error messages are displayed on this line in the case of data transmission Control keys A short keypress switches the DSI SMART Programmer on A long keypress switches the device off When the DSI SMART Programmer is switched on a short keypress causes the program to sw...

Page 3: ...rameter P I R Active inactive off only active With the active setting the lighting is automatically switched on or off depending whether a person is present With the inactive setting the basicDIM ILD DSI SMART PTM can in combination with continuous time delay only be used for lighting control With the off only setting the lighting has to be switched on manually momentary action switch remote contr...

Page 4: ...e momentary action switch twice shortly With the off setting this function is disabled DALIorDSI3 DSI DALI DSI With the DSI setting DSI interface mode is enabled With the DALI setting DALI interface mode in which DALI broadcast commands are sent is enabled Offset Mode4 fixed converging converging This parameter specifies how the adjustable Offset Value of the basicDIM ILD behaves from channel 2 to...

Page 5: ...risk in the top right hand corner indicates that the setting can be modified light level 65 1 100 max man 9 Use the Scroll buttons to select the desired value light level 70 1 100 max man 10 Quit this menu item The previously set value is retained light level 70 1 100 max man 11 Select the next parameter t delay 10 min 30s 60min cont 12 Press Select to make this parameter modifiable Example curren...

Page 6: ...ttings are displayed on the second line light level 65 1 100 max man 4 Select the parameter that is to be modified e g change bright out from yes to no bright out yes yes no 5 Read out the currently set value from the DSI SMART PTM basicDIM ILD bright out yes reading OK 6 Press Select to make this parameter modifiable bright out yes yes no 7 Use the Up Down buttons to change to no bright out no ye...

Page 7: ...d or start automatic lighting control in the DSI SMART PTM basicDIM ILD Function Button Display 1 Switch on the programming device SMART Programmer Version 2 30 2 Go to the IR Remote menu item IR remote 3 Select The lamp off function is then shown on the first line lamp off 4 Select the desired function e g lamp to automatic lamp to auto matic 5 Press Send to transfer to the DSI SMART PTM basicDIM...

Page 8: ...mming problems The maximum range of the DSI SMART Programmer is significantly reduced by using such equipment In such cases it is advisable to use the SMART Controller or the momentary action switch to switch off the lighting before programming 7 Reset DSI SMART PTM basicDIM ILD to factory settings The DSI SMART DSI SMART PTM or basicDIM ILD can be reset to their default factory settings To do thi...

Reviews: