2. Programming the main parameters 

 

2.1. Adjustable parameters 

The DSI-SMART (PTM)/basicDIM ILD provides the following parameters to be set: 
Values in parentheses denote factory parameter settings. 
 

Parameter  

Adjustment 
range

 

(

factory setting)

 

Description 

light level 

1-100/max  
(70) 

Selectable lighting control set point, 1-100 increments. 
“max” also makes it possible to set the control gear to full power. 
(DSI 255) 
“man” indicates whether the adjustment value was overwritten by 
the SET function of the SMART Controller. 

time delay: 

30s - 60min/con 
(20 min) 

Delay time after the last detected movement 
The following values can be set: 
30 seconds, 1, 2, 3, 5, 10, 15, 20, 30, 45 and 60 minutes and 
“continuous” (no switch-off) 

if vacant 

off/30 s - 60 
min/con 
(off)

 

The “off” setting switches the luminaire off after the delay time has 
elapsed. 
If a time value is set, the luminaire dims to the “sec. level” 
parameter and only switches off after the previously set time has 
elapsed. The following values can be set: 
off, 30 seconds, 1, 2, 3, 5, 10, 15, 20, 30, 45 and 60 minutes and 
“continuous” (“never OFF” function) 

sec. level

1

 1%-100% 

(1%) 

Second light level to which luminaire dims after the delay time has 
elapsed. (in conjunction with the “if vacant” parameter) 

P.I.R. Active/inactive/ 

 

off only 
(active) 

With the “active” setting, the lighting is automatically switched on or 
off depending whether a person is present. 
With the “inactive” setting, the basicDIM ILD/DSI-SMART (PTM) 
can, in combination with continuous “time delay”, only be used for 
lighting control. 
With the “off only” setting, the lighting has to be switched on 
manually (momentary-action switch, remote control) but is switched 
off by the presence detector. 

bright-out yes/no 

(yes) 

With the “yes” setting, the lighting switches off as soon as the light 
level exceeds 150% of the set point for longer than 10 minutes, for 
instance, if the room is adequately illuminated by sunlight. If the 
actual value falls below 100% of the set point, the lighting switches 
back on again. 
With the “no” setting, the lighting remains switched on (at the 
minimum dimming level) even if the room is adequately illuminated 
by sunlight and no artificial lighting is required. 

Power up 

on/off 
(on) 

With the “on” setting, the luminaire switches on after a mains break.
With the “off” setting, the luminaire does not switch on after a mains 
break. The presence detector becomes active again after 15 
seconds. 

10% start

2

 on/off 

(on) 

With “on”, the lighting is started at a dimming level of 10%. 
With “off”, the lighting is started at a dimming level of 1%. 

 

 

                                                      

1

 The DSI-SMART PTM and basicDIM ILD support the “sec. level” parameter. 

2

 The “10% start” parameter is only supported by the DSI-SMART. 

Summary of Contents for DSI-SMART

Page 1: ...eneral information 2 1 1 Overview of DSI SMART Programmer 2 2 Programming the main parameters 3 2 1 Adjustable parameters 3 2 2 Programming the entire parameter list 5 2 3 Programming individual parameters 6 3 Monitoring 7 4 Remote control 7 5 System tests 7 6 Status and error messages 8 7 Reset DSI SMART PTM basicDIM ILD to factory settings 8 ...

Page 2: ... the LCD display The lower line the status bar shows the possible settings for the menu item in question the current status and any error messages are displayed on this line in the case of data transmission Control keys A short keypress switches the DSI SMART Programmer on A long keypress switches the device off When the DSI SMART Programmer is switched on a short keypress causes the program to sw...

Page 3: ...rameter P I R Active inactive off only active With the active setting the lighting is automatically switched on or off depending whether a person is present With the inactive setting the basicDIM ILD DSI SMART PTM can in combination with continuous time delay only be used for lighting control With the off only setting the lighting has to be switched on manually momentary action switch remote contr...

Page 4: ...e momentary action switch twice shortly With the off setting this function is disabled DALIorDSI3 DSI DALI DSI With the DSI setting DSI interface mode is enabled With the DALI setting DALI interface mode in which DALI broadcast commands are sent is enabled Offset Mode4 fixed converging converging This parameter specifies how the adjustable Offset Value of the basicDIM ILD behaves from channel 2 to...

Page 5: ...risk in the top right hand corner indicates that the setting can be modified light level 65 1 100 max man 9 Use the Scroll buttons to select the desired value light level 70 1 100 max man 10 Quit this menu item The previously set value is retained light level 70 1 100 max man 11 Select the next parameter t delay 10 min 30s 60min cont 12 Press Select to make this parameter modifiable Example curren...

Page 6: ...ttings are displayed on the second line light level 65 1 100 max man 4 Select the parameter that is to be modified e g change bright out from yes to no bright out yes yes no 5 Read out the currently set value from the DSI SMART PTM basicDIM ILD bright out yes reading OK 6 Press Select to make this parameter modifiable bright out yes yes no 7 Use the Up Down buttons to change to no bright out no ye...

Page 7: ...d or start automatic lighting control in the DSI SMART PTM basicDIM ILD Function Button Display 1 Switch on the programming device SMART Programmer Version 2 30 2 Go to the IR Remote menu item IR remote 3 Select The lamp off function is then shown on the first line lamp off 4 Select the desired function e g lamp to automatic lamp to auto matic 5 Press Send to transfer to the DSI SMART PTM basicDIM...

Page 8: ...mming problems The maximum range of the DSI SMART Programmer is significantly reduced by using such equipment In such cases it is advisable to use the SMART Controller or the momentary action switch to switch off the lighting before programming 7 Reset DSI SMART PTM basicDIM ILD to factory settings The DSI SMART DSI SMART PTM or basicDIM ILD can be reset to their default factory settings To do thi...

Reviews: