2012 Tridonic
Page 3 of 8
2. Programming the main parameters
2.1. Adjustable parameters
The DSI-SMART (PTM)/basicDIM ILD provides the following parameters to be set:
Values in parentheses denote factory parameter settings.
Parameter
Adjustment
range
(
factory setting)
Description
light level
1-100/max
(70)
Selectable lighting control set point, 1-100 increments.
“max” also makes it possible to set the control gear to full power.
(DSI 255)
“man” indicates whether the adjustment value was overwritten by
the SET function of the SMART Controller.
time delay:
30s - 60min/con
(20 min)
Delay time after the last detected movement
The following values can be set:
30 seconds, 1, 2, 3, 5, 10, 15, 20, 30, 45 and 60 minutes and
“continuous” (no switch-off)
if vacant
off/30 s - 60
min/con
(off)
The “off” setting switches the luminaire off after the delay time has
elapsed.
If a time value is set, the luminaire dims to the “sec. level”
parameter and only switches off after the previously set time has
elapsed. The following values can be set:
off, 30 seconds, 1, 2, 3, 5, 10, 15, 20, 30, 45 and 60 minutes and
“continuous” (“never OFF” function)
sec. level
1
1%-100%
(1%)
Second light level to which luminaire dims after the delay time has
elapsed. (in conjunction with the “if vacant” parameter)
P.I.R. Active/inactive/
off only
(active)
With the “active” setting, the lighting is automatically switched on or
off depending whether a person is present.
With the “inactive” setting, the basicDIM ILD/DSI-SMART (PTM)
can, in combination with continuous “time delay”, only be used for
lighting control.
With the “off only” setting, the lighting has to be switched on
manually (momentary-action switch, remote control) but is switched
off by the presence detector.
bright-out yes/no
(yes)
With the “yes” setting, the lighting switches off as soon as the light
level exceeds 150% of the set point for longer than 10 minutes, for
instance, if the room is adequately illuminated by sunlight. If the
actual value falls below 100% of the set point, the lighting switches
back on again.
With the “no” setting, the lighting remains switched on (at the
minimum dimming level) even if the room is adequately illuminated
by sunlight and no artificial lighting is required.
Power up
on/off
(on)
With the “on” setting, the luminaire switches on after a mains break.
With the “off” setting, the luminaire does not switch on after a mains
break. The presence detector becomes active again after 15
seconds.
10% start
2
on/off
(on)
With “on”, the lighting is started at a dimming level of 10%.
With “off”, the lighting is started at a dimming level of 1%.
1
The DSI-SMART PTM and basicDIM ILD support the “sec. level” parameter.
2
The “10% start” parameter is only supported by the DSI-SMART.