2012 Tridonic
Page 8 of 8
6. Status and error messages
Message
Description
sending.... OK
Transfer from programmer to sensor successful
reading.... OK
Transfer from sensor to programmer successful
link error
No reply from DSI-SMART (PTM)/basicDIM ILD
not supported
Command is not supported by the device
Make sure that each transfer is acknowledged by “sending OK” or “reading OK”. Otherwise correct
programming cannot be guaranteed.
Please note: When using electronic ballasts that operate lamps in the 36 kHz range,
interference frequencies generated by the light source may cause programming problems.
The maximum range of the DSI-SMART Programmer is significantly reduced by using such
equipment. In such cases it is advisable to use the SMART Controller or the momentary-
action switch to switch off the lighting before programming.
7. Reset DSI-SMART (PTM)/basicDIM ILD to factory settings
The DSI-SMART, DSI-SMART PTM or basicDIM ILD can be reset to their default factory settings. To
do this, proceed as follows:
Function Button
Display
1
Switch on the programming device
SMART
Programmer
Version 2.30
2
Go to the “Download/Program” menu item
<downld/progr>
3
Select the <downld/progr> menu
download all
4
Select the “restore default” parameter.
restore default
5
Enable the change in the DSI-SMART (PTM)/basicDIM ILD.
restore default
sending.....OK
Technical Sales
September 2012