CONTROLLER SETTINGS
FMS-1655 Isolation Room Pressure Controller Settings
FMS-1655
This form should be completed during the initial configuration for each room pressure controller. Be sure to configure the
unit for either Positive, Negative, or both using the Isolation Mode Configuration setup procedure. See FMS-1655 Wiring and
Installation Manual for details.
Room Name / Number
Unit Model Number and Serial Number (ESN)
Analog Input
Normal Operating Pressure (reading with door closed)
Sensor Input Mode (normal or inverted)
Sensor Input Range (zero-based or offset)
Sensor Pressure Range
Positive Isolation Setpoint
Negative Isolation Setpoint
Neutral Isolation Setpoint
Pressure Deadband
Analog Output
Operating Mode (Direct or PID)
Analog Output Range (zero-based or offset)
Analog Output Upper Limit (0 – 100%)
Analog Output Lower Limit (0 – 100%)
Analog Output Input Channel (AI-1 thru AI-4, TI-1 or TI-2)
Analog Output Action (Direct or Reverse)
Analog Output Range (zero-based or offset)
Door Switch
Operating Mode (normally-open or normally-closed)
Delay Setting (0 - 240 secs)
Relay Output
Trigger Mode (Setpoints, Isolation Mode or Occupancy)
Input Channel (AI-1 thru AI-4, TI-1 or TI-2)
Positive Isolation High Setpoint
Triatek reserves the right to change product specifications without notice.
Summary of Contents for FMS-1655
Page 1: ...FMS 1655 Installation Manual Version 11 15 16 Triatek FMS 1655 Room Pressure Controller ...
Page 2: ...FMS 1655 Triatek reserves the right to change product specifications without notice Notes ...
Page 57: ...FMS 1655 50 Notes Triatek reserves the right to change product specifications without notice ...
Page 63: ...Notes FMS 1655 56 Triatek reserves the right to change product specifications without notice ...