TABLE 8.9: MAXIMUM ALLOWABLE D.H.W. FIRING RATE
(Inputs in Bold are Factory Settings)
BOILER
MODEL
FLOW THROUGH BOILER DURING
CALL FOR D.H.W. (GPM)
MAX.
ALLOWABLE
D.H.W. FIRING
RATE
MAX
ALLOWABLE
D.H.W. FAN
SPEED
BOILER
D.H.W.
OUTPUT
BOILER
I.W.H.
I.W.H. BYPASS
(MBH)
(par. 15/16 - RPM)
(MBH)
T300
8.0
8.0
N/A
168
3250
150
T300
12.7
12.7
N/A
262
5000
245
T300
15.0
15.0
N/A
300
5500
265
T399
T425
12.0
8.0
4.0
254
3000
236
T399
T425
12.7
12.7
N/A
272
3250
245
T399
T425
16
16
N/A
335
4000
310
T399
20.0
20.0
N/A
399
4800
350
T425
22.0
22.0
N/A
425
5000
367
Figure 8.8: Piping Method #1 - Piping Multiple Indirect Water Heaters
41