6) Vertical Terminal Installation
- In addition to the vertical terminal, either a Flat Roof Flashing (100/150 PN
230571) or Sloped Roof Flashing (100/150 PN 230572) is required for this installation.
a) Determine the center line of the terminal location on the roof. If the roof is flat, cut a 6-1/2” diameter hole for
the 100/150 terminal. If the roof is sloped, cut a hole large enough for the terminal to pass through the roof while
remaining plumb.
b) Install the roof flashing using standard practice for the roofing system on the structure.
c) If not already done, assemble the venting system inside the building. The last section of pipe needs to be on the
same center line as the terminal and within 28” of the top edge of the roof flashing (Figure 6.21a).
d) Measure distance “H” from the top edge of the storm collar to the end of the last fitting as shown in Figure 6.21a.
e) Add 1” to distance “H”. Carefully mark this length on the pipe as shown in Figure 6.21b.
f) Cut the
outer pipe only
at the point marked in Step (e) using aviation shears, a hacksaw, or an abrasive wheel
cutter. Be careful to cut the pipe square. De-burr the cut end with a file or emery cloth.
g) Place a mark on the aluminum inner pipe 3/8” beyond the end of the outer pipe (Figure 6.21b). Use a fine tooth
hacksaw to cut the aluminum pipe and be careful to cut the pipe square. De-burr the cut edge of the aluminum
pipe with a file or emery cloth.
h) Make a mark on the terminal section 1” from the cut end of the outer pipe as shown in Figure 6.21b.
i) Slip the terminal section through the roof from the outside. Push into the last section of vent pipe until the mark
made in Step (h) is no longer visible. Secure the terminal to the last piece of pipe with three #10 x 1/2” sheet
metal screws. Drill a 1/8” hole through both outer pipes to start these screws.
Use a drill stop or other means
to ensure that the drill bit does not penetrate more than 3/8” into the outer pipe. Do not use a sheet metal
screw longer than 1/2”.
j) Secure the terminal section to the inside of the roof structure using the mounting bracket provided with the
terminal (Figure 6.21c).
7) Chimney Chase Installation - A vertical vent system can be installed in an unused masonry chimney. This
installation is similar to other vertical installations with the following exceptions (Also see Figure 6.22):
a) The chimney chase elbow kit (100/150 PN 230568) is used at the base of the chimney. This kit consists of
a support elbow and a mounting bracket. Slip the elbow over the M10 x 35 screw in the support bracket.
Determine the desired vertical location of the support elbow in the chimney and mark the location of the pin
on the back of the support bracket on the back wall of the chimney. Drill a 7/16”dia x 2-1/2” deep hole at this
location to support the back of the bracket. The front of the elbow mounting bracket is supported by the bottom
of the opening into the chimney or by an installer supplied bracket.
b) Construct a weather-tight flat roof to cover the top of the old chimney. Install the vertical terminal through this
roof using the flat roof flashing.
28
FIGURE 6.21a: DIMENSION “H”
Summary of Contents for Triumph series
Page 2: ......
Page 34: ...32 FIGURE 6 23 CONDENSATE PIPING ARRANGEMENT ...
Page 48: ...46 Figure 8 14 Multiple Boiler Piping ...
Page 50: ...Figure 9 1 Wiring Connections Diagram 48 ...
Page 51: ...Figure 9 2 Ladder Diagram 49 ...
Page 69: ...67 PAGE INTENTIONALLY LEFT BLANK ...
Page 71: ...69 ...
Page 72: ...70 ...
Page 73: ...71 ...
Page 75: ...73 ...
Page 76: ...74 ...
Page 78: ...76 ...
Page 79: ...77 ...
Page 82: ...80 ...
Page 83: ...81 155 156 158 157 160 159 ...
Page 84: ...82 161 162 164 163 166 165 ...
Page 85: ...83 167 ...